October 2019
Installation, Operation and Maintenance Manual
MAN-02-04-97-0713-EN Rev. 1
126
Appendix
Appendix
B.2
Instructions for Proper Installation
WARNING
Before installation, it is mandatory to check if the nameplate associated with the
extension for additional entry specifies the appropriate degree of protection and ambient
temperature limits as requested by the rules applicable to the plant/location where the
XTE3000 is installed.
Safety warnings and warranty will be invalidated if the XTE3000 is installed in explosive
atmospheres not covered by the appropriate grade of protection, and/or in environments
where temperatures exceed the maximum temperature specified on the product label.
B.2.1
Marking
Figure B-4
Template of the label for XTE3000 / XTE3000AD / XTE3000LP
IECEx INE YY.NNNNX
=
IECEx reference certificate (CoC)
INERIS YY ATEX NNNNX
=
ATEX reference certificate
0080
=
Notified body for ATEX quality assurance (INERIS)
II
=
Group II (surface industries)
2
=
Category 2 apparatus
G
=
Explosive atmospheres caused by gas, mists, or vapors
D
=
Explosive atmospheres caused by gas dusts
IP66/68
=
Degree of protection
Table B-1.
Hazardous zone
Categories according to 2014/34/EU Directive
Gas, mists, or vapors
Zone 0
1G
Gas, mists, or vapors
Zone 1
2G or 1G
Gas, mists, or vapors
Zone 2
3G or 2G or 1G
Dust
Zone 20
1D
Dust
Zone 21
2D or 1D
Dust
Zone 22
3D or 2D or 1D