Appendix C: XTE3000 / XTE3000AD
Ex db h IIC T4 Gb / Ex h tb IIIC T135°C Db IP66/68
Ex db h ia IIC T4 Gb / Ex h tb IIIC T135°C Db IP66/68
C.1
Safety Instructions
C.1.1
General
This Appendix C to Installation, Operation, and Maintenance Manual MAN-02-04-97-0713
prescribes the Safety Instructions applicable to electric actuators XTE3000-010 and
XTE3000-020. The subject actuator is certified according to EN and IEC Standards 60079-0,
60079-1, 60079-11, 60079-31 and EN ISO 80079-36, 80079-37 for protection type Ex db h or
Ex db h ia for gas group IIIC. The actuator is suitable for installation in an ambient temperature
range from -60 °C (-76 °F) to +85 °C (+185 °F).
WARNING
Installation, configuration, commissioning, maintenance, and repairs must be performed
by approved and qualified personnel only.
The XTE3000 is designed in accordance with the applicable international rules and
specifications, but the following regulations must be observed in every case:
•
General installation and safety regulations.
•
The proper use of personal protective devices (glasses, clothing, gloves).
•
The proper use of tools, lifting equipment, and transport equipment.
C.2
Instructions for Proper Installation
WARNING
Verify that the actuator nameplate conforms to the applicable certification, ambient
temperature range, and site safety requirements.
Safety warnings and warranty will be invalidated if the XTE3000 is installed in explosive
atmospheres not covered by the appropriate grade of protection, and/or in environments
where temperatures exceed the maximum temperature specified on the product label.
NOTICE
Check that the label (as shown by the example Figure C-1) is fixed to the unit and is complete
with all the appropriate information.