Installation, Operation and Maintenance Manual
MAN-02-04-97-0713-EN Rev. 1
October 2019
149
Appendix
Appendix
D.7
Installation
NOTICE
Installation must be carried out in accordance to the applicable standards IEC/EN 60079-14
and IEC/EN 60079-17 regarding the electrical installations in Hazardous Areas (other than
mines) classified as Zones 1, 2 (gas) and Zones 21, 22 (dust) following IEC/EN 60079-10-1
and IEC/EN 60079-10-2 and any other applicable national standards and rules.
D.7.1
Working Condition
WARNING
Verify that the actuator nameplate conforms to the applicable certification, ambient
temperature range, and site safety requirements.
D.7.1.1
Models and Temperature
XTE-010, XTE-020 and XTE-030 from -25°C to +60°C (from -13°F to +140°F)
D.7.2
Identification of Entries
D.7.2.1
Base Actuator
The XTE3000 electric actuator is equipped with 5 entries (3 are standard; the 4th and 5th
are supplied upon request).
With reference to Figure D-5, the thread form/size for each entry is as follows:
Table D-4.
Entry
NPT size
Alternative (Metric size ISO 965)
1
1"
M32x1.5
2
1 1/2"
M40x1.5
3
1"
M32x1.5
4 (optional)
3/4"
M25x1.5
5 (optional)
3/4"
M25x1.5