Installation, Operation and Maintenance Manual
MAN-02-04-97-0713-EN Rev. 1
October 2019
83
Section 10: View Routines
View Routines
View Procedure
•
Move the local selector to OFF and then simultaneously press OPEN and STOP.
Select the language according to the instructions (see “Entering the view mode”).
When the message displayed is “VIEW MODE OK?” press YES. Press NO to
scroll through the list of available menus and press YES to select the
"Maintenance" menu.
•
Press NO to scroll through the list of available routines and press YES to select
"Operation Log".
•
Press YES to select general data or press NO to skip to recent data.
•
Press YES to scroll through the list of values.
•
Press YES to view the recent data log or press NO to exit.
•
Press YES to scroll through the list of values.
Table 16.
General Data
Opening time
This datum is only available in the general data log. It is updated at the end
of every full valve stroke of the valve in opening direction. The data of the
previous stroke are lost. It gives the time necessary to the valve to move
from the closed position to the open position, expressed in hours, minutes
and seconds.
Closing time
This datum is only available in the general data log. It is updated at the end
of every full valve stroke of the valve in closing direction. The data of the
previous stroke are lost. It gives the time necessary to the valve to move
from the open position to the closed position, expressed in hours, minutes
and seconds.
Contactor cycles
This number counts the cycles of contactors K1 and K2. The value indicated
in the general data log is also used to generate the “max. contactor cycles”
warning when the maximum allowable number of cycles of the contactor is
reached (see Section 12.11, Diagnostic messages). If the main power is DC
or single phase and the actuator supports modulating duty, the counters
(general and recent) are held to 0.
Motor run time
This number counts the hours with the motor energized.
No power time
This number counts the hours without electrical power.
Utilization rate
This number % is incremented every 200 full strokes of the actuator. It
reaches 100% after 20,000 full strokes.
Temperature min
This is the lowest temperature value (in °C) measured inside the
electronics compartment.
Temperature max
This is the highest temperature value (in °C) measured inside the
electronics compartment.
Term temp min
This is the lowest temperature value (in °C) measured inside the terminal
board enclosure.
Term temp max
This is the highest temperature value (in °C) measured inside the terminal
board enclosure.
Motor temp max
This is the highest temperature value (in °C) measured in the electrical motor.
Thermostat alarms
This counts the number of alarms due to high temperature of the electrical
motor and resultant tripping of the motor thermostat.
Torque alarms
This counts the number of alarms due to high torque in opening and closing.