Installation, Operation and Maintenance Manual
MAN-02-04-97-0713-EN Rev. 1
October 2019
55
Section 9: Set-Up Routines
Set-Up Routines
9.1.2
Torque Set-up
The output torque limits to close or to open may be configured between 40% and 100% of
the nominal torque stated on the actuator nameplate.
Set-up Procedure
•
Move the local selector to OFF and then simultaneously press OPEN and STOP.
Select the language and then enter the password according to the instructions
(refer to “Entering the set-up mode”). When the message displayed is “SET-UP
MODE OK?” press YES. Press YES to select the "Actuator Setup" menu, press NO,
and then press YES to select the "Torque Setup" routine.
•
Press YES if the opening torque limit is correct; otherwise, press NO to scroll
through the list of available values. Press YES when the value is correct.
•
Press YES if the closing torque limit is correct; otherwise, press NO to scroll
through the list of available values. Press YES when the value is correct.
9.1.3
ESD (Emergency Shut Down) Control
An ESD signal can be connected to the actuator to override any existing command and
drive the valve to a predetermined position. The ESD control is not self-maintained: the
ESD action is only performed if the relevant input is active. The ESD control is active when
the 3-position selector is in REMOTE and no alarm is present.
WARNING
The user may select ESD to override the situations indicated by (*). If these situations occur
and if “ESD > ...” is configured, the actuator may be damaged. Therefore, selecting “ESD >
...” will invalidate the warranty.
Function “ESD priority” allows the ESD command to override the following additional
situations: (*) motor thermostat alarm, (*) torque limit tripped, (*) local stop pressed,
3-position selector in LOCAL, 2-speed timer, (*) 3-position selector in OFF.
Configuration procedure
•
Move the local selector to OFF and then simultaneously press OPEN and STOP.
Select the language and then enter the password according to the instructions
(refer to “Entering the set-up mode”). When the message displayed is “SET-UP
MODE OK?” press YES. Press YES to select the "Actuator Setup" menu, press NO to
scroll through the list of available routines, and then press YES to select "ESD Setup".
•
Press YES if the ESD action is correct, or press NO to scroll through the list of
available options (off, open, close, stay-put, go to position xx %). Press YES to
select the desired option.
•
Press either YES or NO to select the signal type (present, absent).