Section 13: Troubleshooting
Troubleshooting
Table 31.
Error List (2)
Error
LED
Indicators
Description
#36: Failsafe not ready
#37: Failsafe ready
L4 flashes
slowly
Failsafe voltage OK and Failsafe not initialized (LUS not
tensioned).
#38: Battery low
#39: Battery OK
L4 is off
Battery on Display board is empty, loss of time/date or counter
values possible.
#44: Inverter error Para
#45 Inverter OK Para
L4 is off
BLDC parameter error.
#46: Analog Input 1
Failure
#47: Analog Input 1 OK
L4 flashes
slowly
SRG active, Positioner live zero detection activated, no setpoint value
recognized.
#48: Analog Input 2
Failure
#49: Analog Input 2 OK
L4 flashes
slowly
Ext. setpoint active, Ext. setpoint live zero detection activated, no
Ext. setpoint value recognized
#30: Oil level low
#31: Oil level OK
–
Binary input on Basis board or switch faulty.
#40: Oil pressure low
#41: Oil pressure OK
–
Analog input (4. . . 20 mA) on Basis board faulty.
#42: Motor protection
#43 Motor protection
OK
–
Binary input on Basis board or switch faulty.