Section 8: Parameter Menu
Parameter Menu
8.10
Parameter Group: Position Output (optional)
Position output is used to indicate the current position of the actuator using 0/4-20 mA;
it can retrofitted using software code. If this option is not enabled, the menu point shows
the message "inactive". No adjustment to the end positions or the travel is required.
Adjustment is automatically performed during the configuration of travel limit positions
(see
Section 18.1
). No further settings are necessary for torque-dependent switch off,
because the controller exclusively uses travel limit positions for the calculation. Regardless
of whether this is defined by the torque or the travel limit positions.
The factory default settings are:
•
4mA at 0% position
•
20mA at 100% position
Table 20.
Position Output Table
Menu Item
Sub Menu
Item
Position
Setting
Notes/Comments
P11.1
Position
Output
Function 1
0: off
mA output disabled.
1: Position
mA output corresponds to the actual position value.
2: Pos.
Valvechar.
mA output corresponds to the actual position value
taking into account the valve characteristic.
3: Torque 1
mA output corresponds to the actual torque value.
4: Torque 2
mA output corresponds to the actual torque value.
Torque = 100% Close: mA output = end
Torque = 0%: mA output = start
Torque = 100% Open: mA output = end
5: Torque 3
mA output corresponds to the actual torque value.
Torque = 150% Close: mA output = start
Torque = 0%: mA output = center
Torque = 150% Open: mA output = end
6: Torque 4
mA output corresponds to the actual torque value.
Torque = 150% Close: mA output = end
Torque = 0%: mA output = start
Torque = 150% Open: mA output = end
P11.2
Position
Output
Start (at 0%)
0 - 20.5 mA
{4 mA}
mA value for the Closed (0%) position
P11.3
Position
Output
End (at 100%)"
0 - 20.5 mA
{20 mA }
mA-value for the On (100%) position
P11.4
Position
Output
Calibration
20mA
-10% - +10%
Calibrating the output position during the setting
of this parameter will output a 20mA (100%) signal.
Use this parameter to calibrate accurately the 20mA
output signal. (e.g., if you measure 19.8mA at the
output, just add 1% (0.2mA - 1% of 20mA) to the
displayed value.
P11.5
Analog
Output
Function 2
see Function
1
P11.6
Analog
Output
Start 2
(at 0%)
see Start
P11.7
Analog
Output
End 2
(at 100%)
see End
P11.8
Analog
Output
Calib. 20mA
2
see
Calib. 20
mA 1