Section 8: Parameter Menu
Parameter Menu
8.3
Parameter Group: Speed
Table 8.
Speed Table
Menu Item
Sub Menu
Item
Position
Setting
2)
Notes/Comments
P4.1
Speed
Local Open
2.5. . . 72.2 rpm
Output speed for local operation in direction OPEN
P4.2
Speed
Local Close
2.5. . . 72.2 rpm
As P4.1 but in direction CLOSE
P4.3
Speed
Remote
Open
2.5. . . 72.2 rpm
Output speed for remote operation in direction
OPEN
P4.4
Speed
Remote
Close
2.5. . . 72.2 rpm
As P4.3 but in direction CLOSE
P4.5
Speed
Emergency
Open AUF
2.5. . . 72.2 rpm
Output speed for emergency operation in direction
OPEN
P4.6
Speed
Emergency
Close
2.5. . . 72.2 rpm
As P4.5 but in direction CLOSE
P4.7
Speed
Torque-
dependent
2.5. . . 72.2 rpm
Seal-tight speed. Speed at which the actuator runs
near the end position at torque-dependent switch
off (see P1.3 and P1.4)
P4.8
Speed
Minimum
2.5. . . 72.2 rpm
1
Minimum speed
2)
representative for CM03
CAUTION: OBSERVE MAXIMUM SPEED
The maximum speed for the 24VDC actuator version is reduced to 20 rpm.
8.4
Parameter Group: Ramp (optional)
The start ramp can be set separately for each operation mode. Thus, a 100% start ramp
means that the motor attains its maximum speed in about a second. Higher speeds (see
Section 18.3
) lead to shorter run times. If the ramp is set below 100%, the starting time
increases in an inversely proportional fashion.
Table 9.
Ramp Table
Menu Item
Sub Menu
Item
Position
Setting
Notes/Comments
P5.1
Ramp
Local
5 - 100%
Start ramp for local operation
P5.2
Ramp
Remote
5 - 100%
Start ramp for remote operation
P5.3
Ramp
Emergency
5 - 100%
Start ramp for emergency operation