Section 8: Parameter Menu
Parameter Menu
8.11
Parameter Group: Step Mode
Step mode operation can be used to extend the operating time in certain ranges or for the
whole travel; it is available in local, remote and emergency mode. Step mode operation can
be activated individually for the directions OPEN and CLOSED. Cycle start, cycle end, cycle
duration and interval time can be set separately for both directions. (see
Figure 62
).
Table 21.
Step Mode Table
Menu Item
Sub Menu
Item
Position
Setting
Notes/Comments
P12.1
Step Mode
Function
Mode
Disabled
Step mode operation is disabled.
Enabled
Step mode operation is enabled in LOCAL,
REMOTE and EMERGENCY operation.
Local only
Step mode mode is only enabled in LOCAL mode.
Remote only
Step mode mode is only enabled in REMOTE mode.
Local +
Remote
only
Step mode is enabled in REMOTE and
LOCAL mode.
P12.2
Step Mode
Function
Start Open
0 - 100%
In OPEN direction, position in % from which the
step mode operation should start.
P12.3
Step mode
Function
End Open
0 - 100%
In OPEN direction, position in % of which the step
mode operation should end.
P12.4
Step Mode
Function
Runtime
Open
0.1 - 60
Runtime in OPEN direction.
P12.5
Step Mode
Function
Pause Time
Open
0.2 - 60
Pause time in OPEN direction.
P12.6
Step Mode
Function
Start Closed
0 - 100%
In CLOSED direction, position in % from which the
step mode operation should start.
P12.7
Step Mode
Function
End Closed
0 - 100%
In CLOSED direction, position in % of which the
step mode operation should end.
P12.8
Step Mode
Function
Runtime
Closed
0.1 - 60
Runtime in Closed direction.
P12.9
Step Mode
Function
Pause Time
0.2 - 60
Pause time in Closed direction.
P12.10
Step Mode
Function
Timebase
0: Seconds
Time basis for run and pause times.
1: Minutes
P12.11
Step mode
function
Speed
adaption
0:
Speed adaption not activated. Normal step
mode function.
1:
Speed adaption is activated. The speed is reduced
according to the runtime and pause time in the step
mode range. (Example: Running time 1 sec and
pause time 1 sec results in half the speed). If the
minimum speed is undershot, the actuator clocks in
the converted ratio with the minimum speed. The
speed adjustment is only applicable to actuators of
the type CM and AB CSC.