Section 8: Parameter Menu
Parameter Menu
8.9
Parameter Group: Binary Outputs
The controller is equipped with 8 freely configurable binary outputs. Please find further
information on technical data of the binary outputs in
Section 28.1
. Provided with external
supply, binary outputs are optically isolated from the rest of the controller.
Default binary outputs are as follows:
Output 1: Ready
Output 2: End position OPEN
Output 3: End position CLOSED
Output 4: Run OPEN
Output 5: Run CLOSED
Output 6: Torque
Output 7: LOCAL
Output 8: REMOTE
Table 16.
Binary Outputs Table (1)
Menu Item
Sub Menu
Item
Position
Setting
Notes/Comments
P10.1
Binary
Output
Output 1
0: User Defined
Optional
1: Ready
Actuator is ready
2: Fault
General fault; actuator is not ready
3: Open
Actuator is in open position
4: Closed
Actuator is in closed position
5: Running Open
Actuators runs in direction Closed
6: Running
Closed
Actuators runs in direction Closed
7: Running
Actuator is running in either Open or Closed
8: Torque Open
Switch off torque was reached in Open
direction-actuator has been switched off
9: Torque Closed
Switch off torque was reached in Closed
direction-actuator has been switched off
10: Torque
Switch off torque was reached in either Closed or
Open direction
11: Travel Open
The Open end postion has been reached
12: Travel Closed
The Closed end postiion has been reached
13: Position >
Int.1
Position > Intermediate position 1
14: Position <
Int.1
Position < Intermediate position 1
15: Position >
Int.2
Position > Intermediate position 2