Section 8: Parameter Menu
Parameter Menu
8.5
Parameter Group: Control
Table 10.
Control Table
Menu Item
Sub Menu
Item
Position
Setting
Notes/Comments
P6.2
Control
Ready delay
0 - 10s
Drop-out delay for the ready signal (Binary outputs)
P6.5
3)
Control
24V output
0
24V auxiliary output is deactivated
(see Section 17.5). The function of the auxiliary
input is still activated.
{1}
24V auxiliary output is activated (see Section 17.5).
P6.6
Control
Min. impuls
0.1 - 2.0 sec
Minimum switch-on time of the motor.
3)
since firmware 1.303
8.6
Parameter Group: Password
The actuator control can be password-protected to prevent access at different levels. It is
possible to prevent entry by unauthorized personnel or to entirely lock motor operation.
Default password is set to "000". You can use both numbers and capital letters in your
password. After entering a password, password protection is activated. To remove
password protection, enter an empty password (000).
When accessing a password-protected parameter, the user is automatically prompted
for the password. Only after correctly entering the password, is it possible to change the
corresponding parameters.
Table 11.
Password Table
Menu Item
Sub Menu
Item
Position
Setting
Notes/Comments
P7.1
Password
Reading
PWD
3- digit
Status display and history data are still viewable;
access to the parameter menu is locked until this
password is introduced. Parameter menu scrolling
is only enabled after entering the password. Electric
motor operation is unlocked.
P7.2
Password
Writing PWD
3- digit
Status display, history data and parameter menu can
be viewed. However, parameters become read-only.
P7.3
Password
Bluetooth
PWD
15-digit
Password for the Bluetooth connection, empty
password deactivates the password request.