Section 8: Parameter Menu
Parameter Menu
Table 14.
Binary Inputs Table (2)
Menu
Item
Sub Menu
Item
Position
Setting
Notes/Comments
P9.1
Binary
Input
Input 1
14: Stop inv.
As STOP but active low.
15: Open
Self-Hold inv.
As Open Self-Hold but active low.
16: Closed
Self-Hold inv.
As Closed Self-Hold but active low.
17: Emergency-
Open inv.
As Emergency-Open but active low.
18: Emergency-
Closed inv.
As Emergency-Closed but active low.
19: Block
With activated (switched) signal, the actuator is
locked for operation also in local mode.
20: Controller
lock
Positioner lock.
21: Release
Local
The actuator may be operated only with a
switched signal.
22: Block Local
As Release Local but active low.
23: Lock Open
Trigger lock OPEN (in LOCAL and REMOTE
mode). Actuator moves with the highest priority to
OPEN; command continues internally active after
reaching the end position OPEN. Dropping only with
LOCK OFF, Supply OFF or operating mode OFF.
24: Lock Closed
Trigger lock CLOSED (in LOCAL and REMOTE
mode). Actuator moves with the highest priority to
CLOSED; command continues internally active after
reaching the end position CLOSED. Dropping only with
LOCK OFF, Supply OFF or operating mode OFF.
25: Lock Off
Drop the lock.
26: Fail-safe
Trigger the Fail-safe function in all operating modes
(only functional in fail-safe actuators).
27: Fail-safe inv.
As Fail-safe, but active low.
28: Lock
Open inv.
As Lock Open, but active low.
29: Lock
Closed inv.
As Lock Open, but active low.
30: Lock Off inv.
As Lock Off, but active low.
31:
Intermediate
position 1
Approach intermediate position 1 (P8.1) in
REMOTE mode (fix position approach). There is no
repositioning upon reaching the intermediate position
within the hysteresis (see P8.6) Higher priority than
intermediate position 2, 3 and 4.