Diagnostics Optimization CT MODBUS RTU Technical Data
E300 Design Guide
431
Issue Number: 1
Auto (2):
After the scope system is reset
Data Logger Data Not Ready
(
Y12
) is set to 1 and the scope begins to acquire data. Once the buffer is full Data
Logger Data Not Ready
(
Y12
) is set to 0 and the scope continues to acquire data.
Data Logger Arm
(
Y11
) has no effect on data acquisition. Provided
Data Logger Data Not Ready
(
Y12
) = 0 and
Data Logger Saving Data
(
Y13
) = 0 it is possible to read the data from the scope buffer as a scope file.
Data acquisition is stopped when the file transfer begins. When the file transfer is complete, data acquisition begins again and
Data Logger Data Not
Ready
(
Y12
) is set to 1 for a period that is long enough to fill the scope buffer with new data.
See
Data Logging Mode
(
Y10
).
See
Data Logging Mode
(
Y10
).
See
Data Logging Mode
(
Y10
).
Data Logger Sample Time
(
Y14
) defines the sample rate of the scope function for all traces in 250
μ
s units (i.e. if
Data Logger Sample Time
(
Y14
) =
4, the sample time is 1 ms).
Data Logger Trigger Delay
(
Y15
) defines how much data is stored before and after the scope is triggered. If
Data Logger Trigger Delay
(
Y15
) = 0 %
then no data is stored before the trigger and all the data is after the trigger. If
Data Logger Trigger Delay
(
Y15
) = 100 % then no data is stored after the
trigger, but all the data is before the trigger.
Y11
Data Logger Arm
Mode
Open-Loop, RFC-A, RFC-S
Minimum
0
Maximum
1
Default
0
Units
Type
1 Bit Volatile
Update Rate
250
μ
s
Display Format
Standard
Decimal Places
0
Coding
RW, NC
Y12
Data Logger Data Not Ready
Mode
Open-Loop, RFC-A, RFC-S
Minimum
0
Maximum
1
Default
Units
Type
1 Bit Volatile
Update Rate
250
μ
s write
Display Format
Standard
Decimal Places
0
Coding
RO, ND, NC, PT
Y13
Data Logger Saving Data
Mode
Open-Loop, RFC-A, RFC-S
Minimum
0
Maximum
1
Default
Units
Type
1 Bit Volatile
Update Rate
Background write
Display Format
Standard
Decimal Places
0
Coding
RO, ND, NC, PT
Y14
Data Logger Sample Time
Mode
Open-Loop, RFC-A, RFC-S
Minimum
1
Maximum
200
Default
1
Units
Type
8 Bit User Save
Update Rate
Background read
Display Format
Standard
Decimal Places
0
Coding
RW, BU
Y15
Data Logger Trigger Delay
Mode
Open-Loop, RFC-A, RFC-S
Minimum
0
Maximum
100
Default
0
Units
%
Type
8 Bit User Save
Update Rate
Background read
Display Format
Standard
Decimal Places
0
Coding
RW