Diagnostics Optimization CT MODBUS RTU Technical Data
318
E300 Design Guide
Issue Number: 1
Date/Time Selector
(
H32
) is used to select the drive date and time as shown in the table below.
When
Date/Time Selector
(
H32
) = 0 the
Date
(
J80
) and
Time
(
J81
) can be written by the user and the values in these parameters are transferred to
the real time clocks in the keypad or any option modules that support this feature that are fitted to the drive. When
Date/Time Selector
(
H32
) is
changed to any other value, the real time clocks are allowed to run normally again. When
Date/Time Selector
(
H32
) is changed from any value to 0
the date and time from a real time clock, if present, is automatically loaded into
Date
(
J80
) and
Time
(
J81
), so that this date and time is used as the
initial value for editing. If more than one real time clock is present the date/time from the keypad is used, if present, and if not then the date/time from
the lowest number slot with a real time clock is used.
Date
(
J80
) and
Time
(
J81
) are used for time stamping trips. These features will continue to use the originally selected clock even if
Date/Time
Selector
(
H32
) is changed until a drive reset is initiated. If
Date/Time Selector
(
H32
) has been changed and a reset is initiated, the trip dates and
times (L41 to L60) are reset to zero.
H32
Date/Time Selector
Mode
Open-Loop, RFC-A, RFC-S
Minimum
0
Maximum
9
Default
1
Units
Type
8 Bit User Save
Update Rate
Background read
Display Format
Standard
Decimal Places
0
Coding
RW, TE
Value
Text
0
Set
1
Powered
2
Running
3
Acc Powered
4
Local Keypad
5
Remote Keypad
6
Slot 1
7
Slot 2
8
Slot 3
9
Slot 4
Date/Time
Selector
(H32)
Date/Time Source
0: Set
Date and time parameters can be written by the user.
1: Power
Time since the drive was powered up.
2: Running
Accumulated drive running time since the drive was manufactured.
3: Acc Power
Accumulated powered-up time since the drive was manufactured.
4: Local Keypad
If a keypad fitted to the front of the drive includes a real-time clock then the date/time from this clock is displayed, otherwise
the date/time is set to zero.
5: Remote Keypad
If a keypad connected to the user comms port of a drive with a 485 includes a real-time clock then the date/time from this clock
is displayed, otherwise the date/time is set to zero.
6: Slot 1
As 4 above, but for option slot 1
7: Slot 2
As 4 above, but for option slot 2
8: Slot 3
As 4 above, but for option slot 3
9: Slot 4
As 4 above, but for option slot 4
H33
Date Format
Mode
Open-Loop, RFC-A, RFC-S
Minimum
0
Maximum
1
Default
0
Units
Type
8 Bit User Save
Update Rate
Background read
Display Format
Standard
Decimal Places
0
Coding
RW, TE
Value
Text
0
Standard
1
US
Summary of Contents for 03200106
Page 490: ...0479 0024 01 ...