Diagnostics Optimization CT MODBUS RTU Technical Data
424
E300 Design Guide
Issue Number: 1
See
Standard Under Voltage Threshold
(
O11
).
See
Standard Under Voltage Threshold
(
O11
).
See
Standard Under Voltage Threshold
(
O11
).
For frame size 07 drives and larger, which use a d.c. link charge system based on a half controlled thyristor input bridge, the rate at which the d.c. bus
is charged can be reduced by setting
Slow Rectifier Charge Rate Enable
(
O17
) to one. This will reduce the charging current which may be required if
significant additional capacitance is added to the d.c. link to prevent rupturing of input fuses.
O14
Low Under Voltage Threshold
Mode
Open-Loop, RFC-A, RFC-S
Minimum
-VM_LOW_UNDER_VOLTS
Maximum
VM_LOW_UNDER_VOLTS
Default
See exceptions below
Units
V
Type
16 Bit User Save
Update Rate
Background read
Display Format
Standard
Decimal Places
0
Coding
RW, VM, RA
Voltage
Default Value
200V
175
400V
330
575V
435
690V
435
O15
Under Voltage Contactor Close Output
Mode
Open-Loop, RFC-A, RFC-S
Minimum
0
Maximum
1
Default
Units
Type
1 Bit Volatile
Update Rate
4 ms write
Display Format
Standard
Decimal Places
0
Coding
RO, ND, NC, PT
O16
Under Voltage System Contactor Closed
Mode
Open-Loop, RFC-A, RFC-S
Minimum
0
Maximum
1
Default
0
Units
Type
1 Bit Volatile
Update Rate
4 ms read
Display Format
Standard
Decimal Places
0
Coding
RW
O17
Slow Rectifier Charge Rate Enable
Mode
Open-Loop, RFC-A, RFC-S
Minimum
0
Maximum
1
Default
0
Units
Type
1 Bit User Save
Update Rate
Background read
Display Format
Standard
Decimal Places
0
Coding
RW