P R O G R A M M I N G
_________________________________________________________________________________
GsmAlarm-500
Software ver. 1.15
-
18-
5.3.1.1.
PARAMETER “A”: INPUT ZONE TRIGGERING CONDITIONS Addr: [201-216]
Input zone triggering conditions
A
XY
Input zone operating mode
X
Y
Input disabled.
0
0
Delay zone. 2)
Without a load resistor when tamper
recognition is off. If tamper recognition
is on (see Ch. 5.3.1.3), 1k
Ω
and 2.2k
Ω
load resistors in series are required.
Triggers when contacts close (NO, see
Ch. 4.2.4).
1
1
24H zone. 3)
Without a load resistor when tamper
recognition is off. If tamper recognition
is on (see Ch. 5.3.1.3), 1k
Ω
and 2.2k
Ω
load resistors in series are required.
Triggers when contacts opened (NC, see
Ch. 4.2.4).
2
2
Fire zone. 4)
EOL mode, load resistor is required (see
Ch. 4.2).
3
3
ON/OFF zone. 5)
ATZ mode. Triggers when contacts
opened (NC). Parallel connected 2.2k
Ω
and 4.7k
Ω
load resistors are required if
tamper recognition is off. 1k
Ω
and
2.2k
Ω
load resistors in series are
required, if tamper recognition is on (see
Ch. 5.3.1.3).
4
4
Follow zone. 6)
2-wire smoke detector connected to the
PGM output C3 1).
5
5
Double-acting delay zone. 7)
ATZ mode with tamper recognition.
Triggers when contacts close (NO).
Tamper recognition must be on, 1k
Ω
and 2.2k
Ω
load resistors in series are
required (see Ch. 4.2.4).
6
6
Double-acting 24-hour zone. 7)
-
-
7
Forced zone with delay. The system can
be armed when the zone is triggered.
Temperature measurement mode. Alarm
is activated if measured temperature
overcomes programmed temperature T.
8
8
Forced follow zone. The system can be
armed when the zone is triggered.
Temperature measurement mode. Alarm
is activated if measured temperature is
lower than programmed temperature T.
9
-
-
1) Only zone Z7 can operate in this mode. PGM output C3 must operate in mode: M01T05 inverted.
2) Zone with programmable delay time. Violation of the protected zone activates alarm only in armed
mode and after expiration of the delay time T.
3) 24-hour zone. Violation of the protected zone activates alarm in armed or disarmed mode. Siren
operates continuously, the delay time is ignored.
4) Fire Zone working in 24 hour mode, the siren is intermittent.