Part 4: Installation and Start-up
Choice of installation
47
Installation 07 = Merlin 1144 => Mixer valve
extension
Terminal assignment
Sensor [Fx] + GND
1 [F9]
optional outdoor sensor (zone control)
2
- - - -
3
- - - -
4 [F5]
Flow sensor Heatcircuit 2
5+6 [FBR]
optional FBR2 (FBR1) for Heatcircuit 1
6 [F2]
optional room sensor for Heatcircuit 1
7
- - - -
8 [F11]
Flow sensor Heatcircuit 1
9
- - - -
10
- - - -
11
- - - -
12 [F15]
optional room sensor for Heatcircuit 2
12+13 [FBR]
optional FBR2 (FBR1) for Heatcircuit 2
14+15
- - - -
16+17
Data line CAN-BUS
18+19
Power supply CAN BUS
Mains [Ax] + N +
20 N-conductor,
mains
21
Power supply, unit
24 [A1]
Pump Heatcircuit 1
25 [A2]
Pump Heatcircuit 2
26
- - - -
27 [A4]
Mixing Valve Heatcircuit 2 open
28 [A5]
Mixing Valve Heatcircuit 2 closed
29-30
- - - -
32-33
- - - -
34 [A8]
Mixing Valve Heatcircuit 1 open
35 [A9]
Mixing Valve Heatcircuit 1 closed
36 [A10]
Booster pump
37
- - - -
38
Power supply of relay via fuse
(e.g. bridge to 22 = L1´)