Choice of installation
Part 4: Installation and Start-up
40
Choice of installation
Installation 01 = Merlin 4034 =>
cascade controller for modulating boiler
Terminal assignment
Sensor [Fx] + GND
1 [F9]
Outdoor sensor
2 [F8]
Header sensor
3 [F6]
Storage tank sensor
4 [F5]
Flow sensor Heatcircuit 2
5+6 [FBR]
optional FBR2 (FBR1) for Heatcircuit 1
6 [F2]
optional room sensor for Heatcircuit 1
7
- - - -
8 [F11]
Flow sensor Heatcircuit 1
9 [F12]
optional hot-water tank lower
10 [F13]
optional Multifunction relay sensor 3
(PT1000; but not for header pump)
11 [F14]
optional Multifunction relay sensor 4
(PT1000; but not if circulation [time]
applies)
12 [F15]
optional room sensor for Heatcircuit 2
12+13 [FBR]
optional FBR2 (FBR1) for Heatcircuit 2
14+15
eBUS (to the heat sources/FA/DCF)
16+17
Data line CAN-BUS
18+19
Power supply CAN BUS
Alternatively: Isolating circuit for
hot water preparation
Mains [Ax] + N +
20 N-conductor,
mains
21
Power supply, unit
24 [A1]
Pump Heatcircuit 1
25 [A2]
Pump Heatcircuit 2
26 [A3]
Cylinder charging pump
27 [A4]
Mixing Valve Heatcircuit 2 open
28 [A5]
Mixing Valve Heatcircuit 2 closed
29+30 [A6] Additional switching HS
32 [A7]
Pump additional switching HS
+ Bridge [33 to 23]
34 [A8]
Mixing Valve Heatcircuit 1 open
35 [A9]
Mixing Valve Heatcircuit 1 closed
36
- - - -
37 [A12]
Circulation pump
38
Power supply of relay via fuse
(e.g. bridge to 22 = L1´)