Part 4: Installation and Start-up
Choice of installation
45
Installation 06 = Merlin 6644 => Pellet and buffer
controller
!
For this installation it is necessary to program the
solar function separately after selecting "06"!
The return flow temperature increase of the pellet
boiler can be implemented using a Lago Basic unit
or a heating circuit function.
MF 4 Func = 23 (Solar)
T-MF4 Setpoint = 60°C (Max DHW-Storage for solar
charge)
MF4 Hyst = 5K Switch on difference
Terminal assignment
Sensor [Fx] + GND
1 [F9]
Outdoor sensor
2 [F8]
Header sensor
3 [F6]
Storage tank sensor
4 [F5]
Flow sensor Heatcircuit 2
5 [F3]
Buffer storage tank sensor Top
6 [F2]
Buffer storage tank sensor Middle
7 [F1]
Buffer storage tank sensor Lower
8 [F11]
Flow sensor Heatcircuit 1
9 [F12]
optional hot-water tank lower
10 [F13]
Solid fuel boiler sensor (HS2: PT1000)
11 [F14]
optional Sol Panel (PT1000)
12 [F15]
optional room sensor for Heatcircuit 2
12+13 [FBR]
optional FBR2 (FBR1) for Heatcircuit 2
14+15
optional eBUS DCF
16+17
Data line CAN-BUS
18+19
Power supply CAN BUS
Mains [Ax] + N +
20 N-conductor,
mains
21
Power supply, unit
24 [A1]
Pump Heatcircuit 1
25 [A2]
Pump Heatcircuit 2
26 [A3]
Cylinder charging pump
27 [A4]
Mixing Valve Heatcircuit 2 open
28 [A5]
Mixing Valve Heatcircuit 2 closed
29+30 [A6] HS1 (pellet boiler)
32+33 [A7] HS2 (Solid fuel boiler)
34 [A8]
Mixing Valve Heatcircuit 1 open
35 [A9]
Mixing Valve Heatcircuit 1 closed
36 [A10]
Pump HS1
37 [A12]
Booster pump / optional solar pump
38
Power supply of relay via fuse
(e.g. bridge to 22 = L1´)