Choice of installation
Part 4: Installation and Start-up
46
Installation 06 = Merlin 6644 => Pellet and buffer
controller with combination storage => with
parameter settings!
!
For this installation it is necessary to change the
following parameters after selecting "06"!
DHW-Load Through must not be activated!
Buffer = 02 (combination storage)
Heatcircuit 2: HC Function = Return flow (Heatcircuit
2 as return flow temperature increase via mixing
valve)
MF 4 Func = 23 (Solar)
T-MF4 Setpoint = 60°C (Max DHW-Storage for solar
charge)
MF4 Hyst = 5K Switch on difference
Terminal assignment
Sensor [Fx] + GND
1 [F9]
Outdoor sensor
2 [F8]
Header sensor
3 [F6]
Storage tank sensor
4 [F5]
Return flow sensor pellet boiler
5 [F3]
Buffer storage tank sensor Top
6 [F2]
Buffer storage tank sensor Middle
7 [F1]
Buffer storage tank sensor Lower
8 [F11]
Flow sensor Heatcircuit 1
9
- - - -
10 [F13]
Solid fuel boiler sensor (HS2: PT1000)
11 [F14]
Sensor Solar Panel (PT1000)
12 [F15]
optional room sensor for Heatcircuit 2
12+13 [FBR]
optional FBR2 (FBR1) for Heatcircuit 2
14+15
optional eBUS DCF
16+17
Data line CAN-BUS
18+19
Power supply CAN BUS
Mains [Ax] + N +
20 N-conductor,
mains
21
Power supply, unit
24 [A1]
Pump Heatcircuit 1
25 [A2]
- - - -
26 [A3]
Cylinder charging pump
27 [A4]
Mixing Valve return flow temperature
increase open
28 [A5]
Mixing Valve return flow temperature
increase closed
29+30 [A6] HS1 (pellet boiler)
32+33 [A7] HS2 (Solid fuel boiler)
34 [A8]
Mixing Valve Heatcircuit 1 open
35 [A9]
Mixing Valve Heatcircuit 1 closed
36 [A10]
Pump HS1
37 [A12]
Booster pump / optional solar pump
38
Power supply of relay via fuse
(e.g. bridge to 22 = L1´)