Part 2: Overview of display values and settings
Service
area
17
Other entries
(Service area)
Use to select a value
Software number
XXX.XX
Software number with index
Cascade manual
operation
(1-8; only with code no.)
Starting different burner stages
of the cascade
Burner time
Burner time for all stages
Burner starts
Burner starts for all stages
STL-Test
Safety temperature limiter test
with heat generator
temperature display =>Start
with F button
(
hold down
)!
Service
(only with code no.)
Input of date or hours for
service messages
Reset User
Load user parameter factory
settings
Reset Expert
(only with code number)
Load expert parameter factory
settings
Reset Time Prog
Load time program factory
settings
Communic BM 1
Remote control HC1 on BUS
Communic BM 2
Remote control HC2 on BUS
Use the F button [End] to exit the level
Software number XXX.XX
Display software number with index (please specify if you
experience problems / have questions about the
controller)
Cascade manual operation (only with code number)
(only for cascades in "Service" operation mode)
Use F button to open level and search using.
After selecting the heat generator with the F button an
output can be selected for this boiler.
With respect to multi-stage heat generators, the second
stage can be activated by means of presetting an output
value > 50%. After closing the service functions the
entries are reset automatically.
Burner time and Burner starts
For example, select "Burner time" (F button).
=> Shows the current values ( )
Reset display: Use the F button to select the boiler and
the level. Use the F button to "Reset"
Use the F button [End]=> to exit the level
STL-test
Start the STL-test (F button). Use to search for the
boiler. Use the F button to select the boiler
=> Display heat generator temperature.
Press and hold the "Start" button until the STL is
activated:
Burner I ON all pumps OFF and all mixers CLOSED
The temperature can be observed in the display.
Service
By date
Activation by entering date for the yearly service
message.
Delete programmed annual message:
Set the value date => year to "Off" (< 01) in the
General/Service/Customer Service level.
After operating hours
Activation by entering operating hours of the installation
after which a service message should be put out.
Delete programmed message:
Set the value Operating H to "Off" (< 50) in the
General/Service/Customer Service level.
Delete the displayed maintenance message
Press the F button, use to set the repeat value to "00",
confirm with F button [OK].
Reset …
The three value groups can be reset to the factory setting
using the Reset function.
Use the F button to select the Reset function, use to
set it to "On" and use the [OK] button to load the standard
values. Use the F button [End] to exit the level (or Home
button).