SINUS/ISD
15P0082B8
USER MANUAL
6 - 35/82
6.4.1.22
LOCAL CONTROL
This block allows the available modes of
Local and Remote operation to be
customised. It also indicates the
selected mode.
Switching between Local and Remote
modes can only be done using the
Operator Station. Refer to Chapter 5:
“The Operator Station” - The L/R Key.
MMI Menu Map
1
SETUP PARAMETERS
2
FUNCTION BLOCKS
3
SEQ & REF
4
LOCAL CONTROL
SEQ MODES
REF MODES
POWER UP MODE
SEQ DIRECTION
REMOTE SEQ
REMOTE REF
LOCAL CONTROL
LOCAL CONTROL
REMOTE SEQ [297] ––TRUE
REMOTE REF [257] ––TRUE
LOCAL/REMOTE –– [298] SEQ MODES
––
LOCAL/REMOTE –– [265] REF MODES
––
REMOTE –– [299] POWER UP MODE ––
FALSE –– [281] SEQ DIRECTION
––
Parameter Descriptions
Parameter Descriptions
SEQ MODES
SEQ MODES
Range: Enumerated - see below
Allows the source of sequencing commands to be selected. Local is the Operator
Station, Remote is an external signal. The modes supported are:
Enumerated Value
:
Seq Mode
0 : LOCAL/REMOTE
1 : LOCAL ONLY
2 : REMOTE ONLY
REF MODES
REF MODES
Range: Enumerated - see below
Allows the source of the reference signal to be selected. Local is the Operator Station,
Remote is an external signal. The modes supported are:
Enumerated Value
:
Ref Mode
0 : LOCAL/REMOTE
1 : LOCAL ONLY
2 : REMOTE ONLY
POWER UP MODE
POWER UP MODE
Range: Enumerated - see below
Allows the power-up operating mode of the inverter to be selected. Local is the Operator
Station, Remote is an external signal, Automatic is the same mode as at power-down.
The modes supported are:
Enumerated Value
:
Power Up Mode
0 : LOCAL
1 : REMOTE
2 : AUTOMATIC
SEQ DIRECTION
SEQ DIRECTION
Range: FALSE / TRUE
When TRUE, direction is a Sequencing command.
When FALSE, direction is a Reference command.
REMOTE SEQ
REMOTE SEQ
Range: FALSE / TRUE
This parameter indicates the present source of the sequencing commands.
REMOTE REF
REMOTE REF
Range: FALSE / TRUE
This parameter indicates the present source of the reference signal.
Summary of Contents for SINUS/ISD 200 S-0.75
Page 56: ...15P0082B8 USER MANUAL SINUS ISD 5 14 14...
Page 144: ...15P0082A8 USER MANUAL SINUS ISD 8 2 2...
Page 166: ...15P0082B8 USER MANUAL SINUS ISD 10 16 16...
Page 180: ...15P0082B8 USER MANUAL SINUS ISD 12 8 8...
Page 184: ...15P0082A8 USER MANUAL SINUS ISD 14 2 2...
Page 186: ...15P0082B8 USER MANUAL SINUS ISD 15 2 12 MACRO1 MACRO1...
Page 188: ...15P0082B8 USER MANUAL SINUS ISD 15 4 12 MACRO2 MACRO2...
Page 190: ...15P0082B8 USER MANUAL SINUS ISD 15 6 12 MACRO3 MACRO3...
Page 192: ...15P0082B8 USER MANUAL SINUS ISD 15 8 12 MACRO4 MACRO4...
Page 194: ...15P0082B8 USER MANUAL SINUS ISD 15 10 12...
Page 195: ...SINUS ISD 15P0082B8 USER MANUAL 15 11 12...
Page 196: ...15P0082B8 USER MANUAL SINUS ISD 15 12 12...
Page 200: ...15P0082B8 USER MANUAL SINUS ISD 16 4 10...