SINUS/ISD
15P0082B8
USER MANUAL
6 - 17/82
6.4.1.8
CURRENT FEEDBACK
This function block allows the user to
match the inverter’s current rating to
the motor under control. The inverter
needs to be programmed with the
motor full-load and no-load
(magnetising) rms line current values.
From this information, magnetising
(flux producing) and torque producing
motor current diagnostics can be
generated.
MMI Menu Map
1
SETUP PARAMETERS
2
FUNCTION BLOCKS
3
MOTOR CONTROL
4
CURRENT FEEDBACK
FULL LOAD CALIB
NO LOAD CALIB
POWER FACTOR
MOTOR CURRENT
MOTOR CURRENT
I MAGNETISING
I MAGNETISING
I TORQUE
I TORQUE
LOAD
FIELD
CURRENT FEEDBACK
CURRENT FEEDBACK
MOTOR CURRENT [ 66] ––
0.00 %
MOTOR CURRENT [ 67] ––
0.0 A
I MAGNETISING [ 68] ––
0.00 %
I MAGNETISING [ 69] ––
0.0 A
I TORQUE [ 70] ––
0.00 %
I TORQUE [ 71] ––
0.0 A
LOAD [ 72] ––
0.00 %
FIELD [ 73] ––
0.00 %
**3.4 A – [ 64] FULL LOAD CALIB
––
**1.9 A –– [ 65] NO LOAD CALIB
––
0.80 –– [242] POWER FACTOR
––
Parameter Descriptions
Parameter Descriptions
FULL LOAD CALIB
FULL LOAD CALIB
Range: 0.0 to 1000.0 A
Set this to the motor nameplate full-load rms line current. The parameter is internally
clamped within the range of 25% to 100% of the inverter current rating.
NO LOAD CALIB
NO LOAD CALIB
Range: 0.0 to 1000.0 A
Set this to the motor no-load rms line current. This is normally between 30% to 40% of
the motor nameplate full-load rms line current. However for small motors this
proportion can be much higher. If in doubt, this information can be obtained from the
motor manufacturer. Alternatively, the parameter should be set to rms line current
drawn from the Inverter when running the motor under no-load at base frequency.
The value of NO LOAD CALIB is internally clamped in the inverter to be within 10% to
90% of the FULL LOAD CALIB setting.
POWER FACTOR
POWER FACTOR
Range: 0.50 to 0.95
Set this to the motor power factor rating given on the nameplate.
MOTOR CURRENT
MOTOR CURRENT
Range: xxx.xh % (h)
This diagnostic contains the level of rms line current being drawn from the inverter and
is seen as a % of the FULL LOAD CALIB setting.
MOTOR CURRENT
MOTOR CURRENT
Range: xxxx.x A
This diagnostic contains the level of rms line current being drawn from the Inverter.
I MAGNETISING
I MAGNETISING
Range: xxx.xh % (h)
This diagnostic contains the level of magnetising (flux producing) rms line current
component being drawn from the inverter and is seen as a % of the FULL LOAD
CALIB setting.
I MAGNETISING
I MAGNETISING
Range: xxxx.x A
This diagnostic contains the level of magnetising (flux producing) rms line current
component being drawn from the Inverter.
Summary of Contents for SINUS/ISD 200 S-0.75
Page 56: ...15P0082B8 USER MANUAL SINUS ISD 5 14 14...
Page 144: ...15P0082A8 USER MANUAL SINUS ISD 8 2 2...
Page 166: ...15P0082B8 USER MANUAL SINUS ISD 10 16 16...
Page 180: ...15P0082B8 USER MANUAL SINUS ISD 12 8 8...
Page 184: ...15P0082A8 USER MANUAL SINUS ISD 14 2 2...
Page 186: ...15P0082B8 USER MANUAL SINUS ISD 15 2 12 MACRO1 MACRO1...
Page 188: ...15P0082B8 USER MANUAL SINUS ISD 15 4 12 MACRO2 MACRO2...
Page 190: ...15P0082B8 USER MANUAL SINUS ISD 15 6 12 MACRO3 MACRO3...
Page 192: ...15P0082B8 USER MANUAL SINUS ISD 15 8 12 MACRO4 MACRO4...
Page 194: ...15P0082B8 USER MANUAL SINUS ISD 15 10 12...
Page 195: ...SINUS ISD 15P0082B8 USER MANUAL 15 11 12...
Page 196: ...15P0082B8 USER MANUAL SINUS ISD 15 12 12...
Page 200: ...15P0082B8 USER MANUAL SINUS ISD 16 4 10...