SINUS/ISD
15P0082B8
USER MANUAL
6 - 51/82
6.4.1.32
RAISE/LOWER
This function block acts an internal
motorised potentiometer (MOP).
The OUTPUT is preserved during the
power-down of the inverter.
Funtional Description
The table below describes how OUTPUT is controlled by the RAISE INPUT, LOWER
INPUT and RESET inputs.
RESET
RAISE
INPUT
LOWER
INPUT
Action
TRUE
Any
Any
OUTPUT tracks RESET VALUE
FALSE
TRUE
FALSE
OUTPUT ramps up to MAX VALUE at RAMP RATE
FALSE
FALSE
TRUE
OUTPUT ramps down to MIN VALUE at RAMP RATE
FALSE
FALSE
FALSE
OUTPUT not changed. *
FALSE
TRUE
TRUE
OUTPUT not changed. *
* If OUTPUT is greater than MAX VALUE the OUTPUT will ramp down to MAX VALUE
at RAMP RATE. If OUTPUT is less than MIN VALUE the OUTPUT will ramp up to MIN
VALUE at RAMP RATE.
IMPORTANT:
Do not set MIN VALUE to greater than MAX VALUE, as the resulting value of OUTPUT
will be unpredictable.
MMI Menu Map
1
SETUP PARAMETERS
2
FUNCTION BLOCKS
3
SETPOINT FUNCS
4
RAISE/LOWER
RAISE INPUT
LOWER INPUT
RL RAMP RATE
RL MAX VALUE
RL MIN VALUE
RL RESET VALUE
RL RESET
RAISE/LOWER OUT
RAISE/LOWER
RAISE/LOWER
OUTPUT [325] –– 0.00 %
FALSE –– [327] RAISE INPUT
––
FALSE –– [328] LOWER INPUT
––
10.0 s –– [326] RAMP RATE
––
100.00 % –– [330] MAX VALUE
––
-100.00 % –– [329] MIN VALUE
––
0.00 % –– [331] RESET VALUE
––
FALSE –– [332] RESET
––
Parameter Descriptions
Parameter Descriptions
RAISE INPUT
RAISE INPUT
Range: FALSE / TRUE
When TRUE causes OUTPUT to ramp up.
LOWER INPUT
LOWER INPUT
Range: FALSE / TRUE
When TRUE causes OUTPUT to ramp down.
RAMP RATE
RAMP RATE
Range: 0.0 to 600.0 s
Rate of change of theOUTPUT . Defined as time to change from 0.00% to 100.00% .
Note that the raise and lower rates are always the same.
MAX VALUE
MAX VALUE
Range: -300.00 to 300.00 %
The maximum value to whichOUTPUT will ramp up to.
MIN VALUE
MIN VALUE
Range: -300.00 to 300.00 %
The minimum value to which OUTPUT will ramp down to.
RESET VALUE
RESET VALUE
Range: -300.00 to 300.00 %
The value the OUTPUT is set to when RESET is TRUE.
RESET
RESET
Range: FALSE / TRUE
When TRUE, forces OUTPUT to track RESET VALUE .
OUTPUT
OUTPUT
Range: xxx.xx %
The ramped output. This parameter is persistent, that is, it is saved throughout a power
failure.
Summary of Contents for SINUS/ISD 200 S-0.75
Page 56: ...15P0082B8 USER MANUAL SINUS ISD 5 14 14...
Page 144: ...15P0082A8 USER MANUAL SINUS ISD 8 2 2...
Page 166: ...15P0082B8 USER MANUAL SINUS ISD 10 16 16...
Page 180: ...15P0082B8 USER MANUAL SINUS ISD 12 8 8...
Page 184: ...15P0082A8 USER MANUAL SINUS ISD 14 2 2...
Page 186: ...15P0082B8 USER MANUAL SINUS ISD 15 2 12 MACRO1 MACRO1...
Page 188: ...15P0082B8 USER MANUAL SINUS ISD 15 4 12 MACRO2 MACRO2...
Page 190: ...15P0082B8 USER MANUAL SINUS ISD 15 6 12 MACRO3 MACRO3...
Page 192: ...15P0082B8 USER MANUAL SINUS ISD 15 8 12 MACRO4 MACRO4...
Page 194: ...15P0082B8 USER MANUAL SINUS ISD 15 10 12...
Page 195: ...SINUS ISD 15P0082B8 USER MANUAL 15 11 12...
Page 196: ...15P0082B8 USER MANUAL SINUS ISD 15 12 12...
Page 200: ...15P0082B8 USER MANUAL SINUS ISD 16 4 10...