SINUS/ISD
15P0082B8
USER MANUAL
6 - 65/82
6.4.1.43
SYSTEM RAMP
This function block forms part of the
reference generation. It provides the
facility to control the rate at which the
inverter will respond to a changing
setpoint demand.
MMI Menu Map
1
SETUP PARAMETERS
2
FUNCTION BLOCKS
3
SEQ & REF
4
SYSTEM RAMP
RAMP TYPE
RAMP ACCEL RATE
RAMP DECEL RATE
RAMP SYM RATE
RAMP SYM MODE
RAMP HOLD
SRAMP CONTINUOUS
SRAMP ACCEL
SRAMP DECEL
SRAMP JERK 1
SRAMP JERK 2
SRAMP JERK 3
SRAMP JERK 4
RAMPING
SYSTEM RAMP
SYSTEM RAMP
RAMPING [698] ––FALSE
LINEAR –– [244] RAMP TYPE
––
10.0 s –– [258] ACCEL RATE
––
10.0 s –– [259] DECEL RATE
––
10.0 s –– [267] SYMETRIC RATE
––
FALSE –– [268] SYMETRIC MODE
––
FALSE –– [260] RAMP HOLD
––
TRUE –– [691] SRAMP CONTINUOUS ––
10.00 % –– [692] SRAMP ACCEL
––
10.00 % –– [693] SRAMP DECEL
––
10.00 % –– [694] SRAMP JERK 1
––
10.00 % –– [695] SRAMP JERK 2
––
10.00 % –– [696] SRAMP JERK 3
––
10.00 % –– [697] SRAMP JERK 4
––
Parameter Descriptions
Parameter Descriptions
RAMP TYPE
RAMP TYPE
Range: Enumerated - see below
Select the ramp type:
Enumerated Value
:
Ramp Type
0 : LINEAR
1 : S
ACCEL RATE
ACCEL RATE
Range: 0.0 to 600.0 s
The time that the inverter will take to ramp the setpoint, from 0.00% to 100.00%.
DECEL RATE
DECEL RATE
Range: 0.0 to 600.0 s
The time that the inverter will take to ramp from the setpoint, from 100.00% to 0.00%.
SYMETRIC RATE
SYMETRIC RATE
Range: 0.0 to 600.0 s
The time that the inverter will take to ramp from 0.00% to 100.00% and from 100.00% to
0.00% when SYMETRIC MODE is TRUE.
SYMETRIC MODE
SYMETRIC MODE
Range: FALSE / TRUE
Select whether to use the ACCEL RATE and DECEL RATE pair of ramp rates, or to use
the SYMETRIC RATE parameter to define the ramp rate for the inverter.
RAMP HOLD
RAMP HOLD
Range: FALSE / TRUE
When TRUE the output of the ramp is held at its last value.
SRAMP CONTINUOUS
SRAMP CONTINUOUS
Range: FALSE / TRUE
When TRUE and the S ramp is selected, forces a smooth transition if the speed setpoint
is changed when ramping. The curve is controlled by the SRAMP ACCEL and SRAMP
JERK 1 to SRAMP JERK 4 parameters. When FALSE, there is an immediate transition
from the old curve to the the new curve.
SRAMP ACCEL
SRAMP ACCEL
Range: 0.00 to 100.00 %
Sets the acceleration rate in units of percent per second², i.e. if the full speed of the
machine is 1.25m/s then the acceleration will be:
1.25 x 75.00% = 0.9375m/s²
SRAMP DECEL
SRAMP DECEL
Range: 0.00 to 100.00 %
This functions in the same way as SRAMP ACCEL above.
Summary of Contents for SINUS/ISD 200 S-0.75
Page 56: ...15P0082B8 USER MANUAL SINUS ISD 5 14 14...
Page 144: ...15P0082A8 USER MANUAL SINUS ISD 8 2 2...
Page 166: ...15P0082B8 USER MANUAL SINUS ISD 10 16 16...
Page 180: ...15P0082B8 USER MANUAL SINUS ISD 12 8 8...
Page 184: ...15P0082A8 USER MANUAL SINUS ISD 14 2 2...
Page 186: ...15P0082B8 USER MANUAL SINUS ISD 15 2 12 MACRO1 MACRO1...
Page 188: ...15P0082B8 USER MANUAL SINUS ISD 15 4 12 MACRO2 MACRO2...
Page 190: ...15P0082B8 USER MANUAL SINUS ISD 15 6 12 MACRO3 MACRO3...
Page 192: ...15P0082B8 USER MANUAL SINUS ISD 15 8 12 MACRO4 MACRO4...
Page 194: ...15P0082B8 USER MANUAL SINUS ISD 15 10 12...
Page 195: ...SINUS ISD 15P0082B8 USER MANUAL 15 11 12...
Page 196: ...15P0082B8 USER MANUAL SINUS ISD 15 12 12...
Page 200: ...15P0082B8 USER MANUAL SINUS ISD 16 4 10...