5-114
PERFORMANCE DATA & PRESSURE CURVES
Revision Y05-03
Service Manual - WNG
5.84.2
Heating Mode at 7.5m Tubing Connection.
230V : Indoor Fan at High Speed.
ENTERING AIR DB ID COIL ( °C)
15
20
25
ENTERING AIR WB
OU COIL (°C)
TH
PI
TH
PI
TH
PI
-10
4.62 2.40 4.44 2.56 4.27 2.69
-7
4.97 2.46 4.80 2.60 4.62 2.74
-2
5.28 2.49 5.10 2.64 4.93 2.79
2
6.42 2.61 6.16 2.78 5.90 2.94
6
9.06 2.81
8.80 3.00
8.49 3.19
10
9.86 2.96 9.59 3.17 9.33 3.38
15
10.65 3.09 10.38 3.33 10.12 3.54
20
11.22 3.18 10.96 3.45 10.65 3.72
*
the above chart includes the weighted deicing infleuence.
LEGEND
TH –
Total Heating Capacity, kW
PI
– Power Input, kW
WB –
Wet Bulb Temp., (
o
C)
DB –
Dry Bulb Temp., (
o
C)
ID
–
Indoor
OU –
Outdoor
5.85
Capacity Correction Factor Due to Tubing Length
5.85.1 Cooling
TOTAL TUBING LENGTH (One Way)
3m
7.5m
10m
15m
20m
25m
30m
40m
50m
1.12
1
0.979
0.943
0.940
0.931
0.927
---
---
*
Minimum recommended tubing length between indoor and outdoor units is 3m.
5.85.2 Heating
TOTAL TUBING LENGTH (One Way)
3m
7.5m
10m
15m
20m
25m
30m
40m
50m
1.01
1
0.994
0.984
0.973
0.963
0.952
---
---
*
Minimum recommended tubing length between indoor and outdoor units is 3m.
Summary of Contents for GC 22 ST
Page 47: ...4 5 OUTLINE DIMENSIONS Revision Y05 03 Service Manual WNG 4 9 OU8 33 RC ST 4 10 OU10 36 RC ST...
Page 71: ...5 24 PERFORMANCE DATA PRESSURE CURVES Revision Y05 03 Service Manual WNG 5 18 2 Heating...
Page 91: ...5 44 PERFORMANCE DATA PRESSURE CURVES Revision Y05 03 Service Manual WNG 5 33 2 Heating...
Page 95: ...5 48 PERFORMANCE DATA PRESSURE CURVES Revision Y05 03 Service Manual WNG 5 36 2 Heating...