5-74
PERFORMANCE DATA & PRESSURE CURVES
Revision Y05-03
Service Manual - WNG
5.55.2
Heating Mode at 7.5m Tubing Connection.
230V : Indoor Fan at High Speed.
ENTERING AIR DB ID COIL ( °C)
15
20
25
ENTERING AIR WB
OU COIL (°C)
TH
PI
TH
PI
TH
PI
-10
1.22 0.54 1.17 0.58 1.13 0.61
-7
1.31 0.56 1.26 0.59 1.22 0.62
-2
1.39 0.56 1.35 0.60 1.30 0.63
2
1.69 0.59 1.62 0.63 1.55 0.67
6
2.39 0.64
2.32 0.68
2.24 0.72
10
2.60 0.67 2.53 0.72 2.46 0.77
15
2.81 0.70 2.74 0.75 2.67 0.80
20
2.96 0.72 2.89 0.78 2.81 0.84
*
the above chart includes the weighted deicing infleuence.
LEGEND
TH –
Total Heating Capacity, kW
PI
– Power Input, kW
WB –
Wet Bulb Temp., (
o
C)
DB –
Dry Bulb Temp., (
o
C)
ID
–
Indoor
OU –
Outdoor
5.56
Capacity Correction Factor Due to Tubing Length
5.56.1 Cooling
TOTAL TUBING LENGTH (One Way)
3m
7.5m
10m
15m
20m
25m
30m
40m
50m
1.03
1
0.983
0.948
---
---
---
---
---
*
Minimum recommended tubing length between indoor and outdoor units is 3m.
5.56.2 Heating
TOTAL TUBING LENGTH
3m
7.5m
10m
15m
20m
25m
30m
40m
50m
1.02
1
0.985
0.955
---
---
---
---
---
*
Minimum recommended tubing length between indoor and outdoor units is 3m.
Summary of Contents for GC 22 ST
Page 47: ...4 5 OUTLINE DIMENSIONS Revision Y05 03 Service Manual WNG 4 9 OU8 33 RC ST 4 10 OU10 36 RC ST...
Page 71: ...5 24 PERFORMANCE DATA PRESSURE CURVES Revision Y05 03 Service Manual WNG 5 18 2 Heating...
Page 91: ...5 44 PERFORMANCE DATA PRESSURE CURVES Revision Y05 03 Service Manual WNG 5 33 2 Heating...
Page 95: ...5 48 PERFORMANCE DATA PRESSURE CURVES Revision Y05 03 Service Manual WNG 5 36 2 Heating...