PERFORMANCE DATA & PRESSURE CURVES
Revision Y05-03
Service Manual - WNG
5.64.2
Heating Mode at 7.5m Tubing Connection.
230V : Indoor Fan at High Speed.
ENTERING AIR DB ID COIL ( °C)
15
20
25
ENTERING AIR WB
OU COIL (°C)
TH
PI
TH
PI
TH
PI
-10
2.49 1.35 2.40 1.44 2.30 1.51
-7
2.68 1.39 2.59 1.46 2.49 1.54
-2
2.85 1.40 2.76 1.49 2.66 1.57
2
3.47 1.47 3.33 1.56 3.18 1.66
6
4.89 1.58
4.75 1.69
4.58 1.79
10
5.32 1.67 5.18 1.78 5.04 1.91
15
5.75 1.74 5.61 1.88 5.46 1.99
20
6.06 1.79 5.91 1.94 5.75 2.10
*
the above chart includes the weighted deicing infleuence.
LEGEND
TH –
Total Heating Capacity, kW
PI
– Power Input, kW
WB –
Wet Bulb Temp., (
o
C)
DB –
Dry Bulb Temp., (
o
C)
ID
–
Indoor
OU –
Outdoor
5.65
Capacity Correction Factor Due to Tubing Length
5.65.1 Cooling
TOTAL TUBING LENGTH (One Way)
3m
7.5m
10m
15m
20m
25m
30m
40m
50m
1.04
1
0.978
0.935
---
---
---
---
---
*
Minimum recommended tubing length between indoor and outdoor units is 3m.
5.65.2 Heating
TOTAL TUBING LENGTH (One Way)
3m
7.5m
10m
15m
20m
25m
30m
40m
50m
1.02
1
0.990
0.970
---
---
---
---
---
*
Minimum recommended tubing length between indoor and outdoor units is 3m.
Summary of Contents for GC 22 ST
Page 47: ...4 5 OUTLINE DIMENSIONS Revision Y05 03 Service Manual WNG 4 9 OU8 33 RC ST 4 10 OU10 36 RC ST...
Page 71: ...5 24 PERFORMANCE DATA PRESSURE CURVES Revision Y05 03 Service Manual WNG 5 18 2 Heating...
Page 91: ...5 44 PERFORMANCE DATA PRESSURE CURVES Revision Y05 03 Service Manual WNG 5 33 2 Heating...
Page 95: ...5 48 PERFORMANCE DATA PRESSURE CURVES Revision Y05 03 Service Manual WNG 5 36 2 Heating...