3-1
RATING CONDITIONS
Revision Y05-03
Service Manual - WNG
3. RATING
CONDITIONS
Standard conditions in accordance with ISO 5151, ISO 13253 (for ducted units)
and EN 14511.
Cooling:
Indoor: 27
o
C DB 19
o
C WB
Outdoor: 35
o
C DB
Heating:
Indoor: 20
o
C DB
Outdoor: 7
o
C DB 6
o
C WB
3.1 Operating
Limits
3.1.1 R410A
Indoor
Outdoor
Cooling
Upper limit
32
o
C DB 23
o
C WB
46
o
C DB
Lower limit
21
o
C DB 15
o
C WB
21
o
C DB
Heating
Upper limit
27
o
C DB
24
o
C DB 18
o
C WB
Lower limit
20
o
C DB
-9
o
C DB -10
o
C WB
Voltage
1PH
198 – 264 V
3PH
360 – 440 V
3.1.2 R407C
Indoor
Outdoor
Cooling
Upper limit
32
o
C DB 23
o
C WB
46
o
C DB
Lower limit
21
o
C DB 15
o
C WB
21
o
C DB
Heating
Upper limit
27
o
C DB
24
o
C DB 18
o
C WB
Lower limit
20
o
C DB
-9
o
C DB -10
o
C WB
Voltage
1PH
198 – 264 V
3PH
360 – 440 V
3.1.3 R22
Indoor
Outdoor
Cooling
Upper limit
32
o
C DB 23
o
C WB
46
o
C DB
Lower limit
21
o
C DB 15
o
C WB
10
o
C DB
Heating
Upper limit
27
o
C DB
24
o
C DB 18
o
C WB
Lower limit
10
o
C DB
-5
o
C DB -6
o
C WB
Voltage
1PH
198 – 264 V
3PH
360 – 440 V
Summary of Contents for GC 22 ST
Page 47: ...4 5 OUTLINE DIMENSIONS Revision Y05 03 Service Manual WNG 4 9 OU8 33 RC ST 4 10 OU10 36 RC ST...
Page 71: ...5 24 PERFORMANCE DATA PRESSURE CURVES Revision Y05 03 Service Manual WNG 5 18 2 Heating...
Page 91: ...5 44 PERFORMANCE DATA PRESSURE CURVES Revision Y05 03 Service Manual WNG 5 33 2 Heating...
Page 95: ...5 48 PERFORMANCE DATA PRESSURE CURVES Revision Y05 03 Service Manual WNG 5 36 2 Heating...