5-22
PERFORMANCE DATA & PRESSURE CURVES
Revision Y05-03
Service Manual - WNG
5.16.2
Heating Mode at 7.5m Tubing Connection.
230V : Indoor Fan at High Speed.
ENTERING AIR DB ID COIL ( °C)
15
20
25
ENTERING AIR
WB OU COIL ( °C)
TH
PI
TH
PI
TH
PI
-10
3.41 1.60 3.28 1.70 3.15 1.79
-7
3.67 1.64 3.54 1.73 3.41 1.82
-2
3.90 1.66 3.77 1.76 3.64 1.86
2
4.75 1.74 4.55 1.85 4.36 1.96
6
6.70 1.87
6.50 2.00
6.27 2.12
10
7.28 1.97 7.09 2.11 6.89 2.26
15
7.87 2.06 7.67 2.22 7.48 2.36
20
8.29 2.12 8.09 2.30 7.87 2.48
*
the above chart includes the weighted deicing infleuence.
LEGEND
TH –
Total Heating Capacity, kW
PI
– Power Input, kW
WB –
Wet Bulb Temp., (
o
C)
DB –
Dry Bulb Temp., (
o
C)
ID
–
Indoor
OU –
Outdoor
5.17
Capacity Correction Factor Due to Tubing Length
5.17.1 Cooling
TOTAL TUBING LENGTH
3m
7.5m
10m
15m
20m
25m
30m
40m
50m
1.02
1
0.961
0.950
---
---
---
---
---
*
Minimum recommended tubing length between indoor and outdoor units is 3m.
5.17.2 Heating
TOTAL TUBING LENGTH
3m
7.5m
10m
15m
20m
25m
30m
40m
50m
1.04
1
0.975
0.961
---
---
---
---
---
*
Minimum recommended tubing length between indoor and outdoor units is 3m.
Summary of Contents for GC 22 ST
Page 47: ...4 5 OUTLINE DIMENSIONS Revision Y05 03 Service Manual WNG 4 9 OU8 33 RC ST 4 10 OU10 36 RC ST...
Page 71: ...5 24 PERFORMANCE DATA PRESSURE CURVES Revision Y05 03 Service Manual WNG 5 18 2 Heating...
Page 91: ...5 44 PERFORMANCE DATA PRESSURE CURVES Revision Y05 03 Service Manual WNG 5 33 2 Heating...
Page 95: ...5 48 PERFORMANCE DATA PRESSURE CURVES Revision Y05 03 Service Manual WNG 5 36 2 Heating...