5-70
PERFORMANCE DATA & PRESSURE CURVES
Revision Y05-03
Service Manual - WNG
5.52.2
Heating Mode at 7.5m Tubing Connection.
230V : Indoor Fan at High Speed.
ENTERING AIR DB ID COIL ( °C)
15
20
25
ENTERING AIR
WB OU COIL (°C)
TH
PI
TH
PI
TH
PI
-10
4.81 2.66 4.63 2.84 4.44 2.98
-7
5.18 2.73 4.99 2.88 4.81 3.04
-2
5.50 2.76 5.31 2.93 5.13 3.10
2
6.69 2.90 6.41 3.08 6.14 3.26
6
9.43 3.11
9.16 3.33
8.84 3.54
10
10.26 3.29 9.98 3.51 9.71 3.76
15
11.08 3.43 10.81 3.70 10.53 3.93
20
11.68 3.53 11.40 3.83 11.08 4.13
*
the above chart includes the weighted deicing infleuence.
LEGEND
TH –
Total Heating Capacity, kW
PI
– Power Input, kW
WB –
Wet Bulb Temp., (
o
C)
DB –
Dry Bulb Temp., (
o
C)
ID
–
Indoor
OU –
Outdoor
5.53.1 Cooling
TOTAL TUBING LENGTH (One Way)
3m
7.5m
10m
15m
20m
25m
30m
40m
50m
1.02
1
0.990
0.971
0.952
0.933
0.914
---
---
*
Minimum recommended tubing length between indoor and outdoor units is 3m.
5.53.2 Heating
TOTAL TUBING LENGTH (One Way)
3m
7.5m
10m
15m
20m
25m
30m
40m
50m
1.01
1
0.994
0.984
0.973
0.963
0.952
---
---
*
Minimum recommended tubing length between indoor and outdoor units is 3m.
Summary of Contents for GC 22 ST
Page 47: ...4 5 OUTLINE DIMENSIONS Revision Y05 03 Service Manual WNG 4 9 OU8 33 RC ST 4 10 OU10 36 RC ST...
Page 71: ...5 24 PERFORMANCE DATA PRESSURE CURVES Revision Y05 03 Service Manual WNG 5 18 2 Heating...
Page 91: ...5 44 PERFORMANCE DATA PRESSURE CURVES Revision Y05 03 Service Manual WNG 5 33 2 Heating...
Page 95: ...5 48 PERFORMANCE DATA PRESSURE CURVES Revision Y05 03 Service Manual WNG 5 36 2 Heating...