5-46
PERFORMANCE DATA & PRESSURE CURVES
Revision Y05-03
Service Manual - WNG
5.34.2
Heating Mode at 7.5m Tubing Connection.
230V : Indoor Fan at High Speed.
ENTERING AIR DB ID COIL ( °C)
15
20
25
ENTERING AIR
WB OU COIL (°C)
TH
PI
TH
PI
TH
PI
-10
5.88 2.72 5.66 2.90 5.43 3.04
-7
6.33 2.79 6.10 2.94 5.88 3.10
-2
6.72 2.82 6.50 2.99 6.27 3.16
2
8.18
2.96
7.84 3.15 7.50 3.33
6
11.54
3.18
11.20 3.40
10.81 3.61
10
12.54 3.36 12.21 3.59 11.87 3.84
15
13.55 3.50 13.22 3.77 12.88 4.01
20
14.28 3.60 13.94 3.91 13.55 4.22
*
the above chart includes the weighted deicing infleuence.
LEGEND
TH –
Total Heating Capacity, kW
PI
– Power Input, kW
WB –
Wet Bulb Temp., (
o
C)
DB –
Dry Bulb Temp., (
o
C)
ID
–
Indoor
OU –
Outdoor
5.35
Capacity Correction Factor Due to Tubing Length
5.35.1 Cooling
TOTAL TUBING LENGTH
3m
7.5m
10m
15m
20m
25m
30m
40m
50m
1.02
1
0.99
0.98
0.98
0.97
0.96
0.95
0.92
*
Minimum recommended tubing length between indoor and outdoor units is 3m.
5.35.2 Heating
TOTAL TUBING LENGTH
3m
7.5m
10m
15m
20m
25m
30m
40m
50m
1.04
1
0.99
0.99
0.98
0.98
0.97
0.96
0.95
*
Minimum recommended tubing length between indoor and outdoor units is 3m.
Summary of Contents for GC 22 ST
Page 47: ...4 5 OUTLINE DIMENSIONS Revision Y05 03 Service Manual WNG 4 9 OU8 33 RC ST 4 10 OU10 36 RC ST...
Page 71: ...5 24 PERFORMANCE DATA PRESSURE CURVES Revision Y05 03 Service Manual WNG 5 18 2 Heating...
Page 91: ...5 44 PERFORMANCE DATA PRESSURE CURVES Revision Y05 03 Service Manual WNG 5 33 2 Heating...
Page 95: ...5 48 PERFORMANCE DATA PRESSURE CURVES Revision Y05 03 Service Manual WNG 5 36 2 Heating...