These pages display the last 5 swells recorded (if any occurred).
NOTE
: according to Standard EN50160, a "swell" is defined as an increase of one or more
phase voltages above 110% of nominal V (See Setup, Sect. 4.2.10). However, a different
threshold may be set by the user.
The Start Date and Time, Affected Phase(s), and Duration of each swell are displayed.
When scrolling through the EN50160 Menu, the page of the most recent swell is displayed
automatically.
To view any previous swells, scroll through the relevant pages using the
⊳
and keys.
5.2.9 - Alarms Menu
This menu stores and displays the last 5 alarms to go off (if any did go off) (For Alarm Setup, see Sect. 4.2.11).
The menu automatically displays the page of the most recent alarm.
Each alarm is identified by:
●
Start Date and Time;
●
type of parameter that exceeded the thresholds set;
●
value of the parameter which caused the alarm to go off;
●
duration of the event.
To view any previous alarms, scroll through the relevant pages using the
⊳
and keys.
NOTE
: Alarms are stored - hence displayed - only at the end of the event, i.e. when the parameter in question
falls within the set values again.
5.2.10 - Transients Menu
This menu can be used to capture and analyse temporary signal-specific
phenomena and variations, such as:
•
Fast transient events (Sect. 5.2.10.1).
•
Inrush currents (Sect. 5.2.10.2).