Man. NVIP3 – Rel 1.3 EN (UK)
- 25 -
4.2.12 - Alarm Setup & Reset
Two alarms can be set and configured with NanoVIP
3
.
●
Place the cursor
on
either alarm and press
to access the
relevant configuration submenu.
●
●
●
●
●
•
Select ALARM RESET and choose
YES
to reset all the stored alarms
that can be viewed in the Alarm Menu (Sect. 5.2.8).
4.2.12.1 - Alarm Configuration
●
In the Alarm 1 or 2 configuration submenu, select
OFF
to disable
the alarm or set the desired parameter to enable the alarm. The
following parameters are available:
Vrms 3F, Vrms L1, Vrms L2, Vrms L3, Irms 3F, Irms L1, Irms L2,
Irms L3, Prms 3F, Prms L1, Prms L2, Prms L3, Qrms 3F, Qrms L1,
Qrms L2, Qrms L3, Srms 3F, Srms L1, Srms L2, Srms L3, pf 3F, pf
L1, pf L2, pf L3, thdv 3F, thdv L1, thdv L2, thdv L3, thdi 3F, thdi L1,
thdi L2, thdi L3, Freq, In, Unbal, Vaux, Iaux, Paux, Qaux, Saux,
PFaux, FRaux, CosPhi L1, CosPhi L2, CosPhi L3.
●
Set the minimum threshold value.
●
Set the maximum threshold value.
●
Set the hysteresis percentage (valid for both the minimum and
maximum threshold).
●
Set the number of events after which the alarm should go off.
●
Return to the "Alarm Setup & Reset" page
NOTE:
if one of the alarms set goes off, it will be indicated in the bottom bar of the
measurement pages, where the alarm will be displayed permanently (scrolling
through measurements, as described in Sect. 4.2.8, will stop) until it is cleared.
The last 5 alarms which have gone off are stored and can be displayed in the relevant menu (Sect. 5.2.8).