Application manual
Air quality multisensor and regulator EK-ES2-TP
Release 1.0 - Updated: 14/02/2020
Application Manual
© EKINEX S.p.A. - All rights reserved
Page 23
Parameter name
Conditions
Values
Filter type
Relative humidity sensor =
enabled
low
medium
high
Low = average value every 4 measurements
Medium = average value every 16 measurements
High = average value every 64 measurements
Humidity offset
Relative humidity sensor =
enabled
0 %
[range –10 % … +10 %]
Minimum change of value to send [%]
Relative humidity sensor =
enabled
2
[range 0 % … +10 %]
If the parameter is set to 0 (zero), no value is sent after a change.
Cyclic sending interval
Relative humidity sensor =
enabled
no sending
[other values in the range 30 s … 120 min]
Threshold 1
Relative humidity sensor =
enabled
not active
below
above
Value [%]
Relative humidity sensor =
enabled,
Threshold 1 = below or above
65
[range 0 … 100]
Threshold value update from bus
Relative humidity sensor =
enabled,
Threshold 1 = below or above
no
/ yes
Threshold lock enable
Relative humidity sensor =
enabled,
Threshold 1 = below or above
no
/ yes
Behaviour at lock
Relative humidity sensor =
enabled,
Threshold 1 = below or above
Threshold lock enable = yes
none
/ off / on
Behaviour at bus recovery
Relative humidity sensor =
enabled,
Threshold 1 = below or above
Threshold lock enable = yes
previous state
/ lock /
unlock
Threshold 2
Relative humidity sensor =
enabled
not active
below
above
Value [%]
Relative humidity sensor =
enabled,
Threshold 2 = below or above
65
[range 0 … 100]
Threshold value update from bus
Relative humidity sensor =
enabled,
Threshold 2 = below or above
no
/ yes