Application manual
Air quality multisensor and regulator EK-ES2-TP
Release 1.0 - Updated: 14/02/2020
Application Manual
© EKINEX S.p.A. - All rights reserved
Page 61
7.8.2
Humidification
The secondary folder
Humidification
includes the following parameters:
Operating modes where humidification is active
Relative humidity setpoint for humidification control [%]
Dehumidification control hysteresis [%]
Cyclic sending interval
Disable from bus
7.8.2.1
Parameter and communication object tables
Parameter name
Conditions
Values
Humidification function
Temperature control
Settings
Thermostat function = both heating and
cooling
disabled
cooling
heating
both cooling and heating
Temperature control
Settings
Thermostat function = heating
disabled
/ heating only
Temperature control
Settings
Thermostat function = heating
disabled
/ cooling only
Parameter that selects the humidification function.
Humidity setpoint
Humidification function
≠ disabled
35
[range 20
… 80 %]
Humidity hysteresis [%]
Humidification function
≠ disabled
0,8 %
[other values in the range
0,5 … 4%]
Cyclic sending interval
Humidification function
≠ disabled
no sending
[other values in the range
30 s … 120
min]
Disable humidification control from bus
Humidification function
≠ disabled
no
/ yes
Signal from bus
Humidification function
≠ disabled
Disable humidification control from bus =
yes
not inverted
/ inverted
Object name
Conditions
Dim.
Flags
DPT
Comm. Obj.
No.
Relative humidity setpoint for
humidification
Humidification
function
≠ disabled
2 bytes
CRWTU
[9.007] humidity (%)
75
Humidification command
Humidification
function
≠ disabled
1 bit
CR-T-
[1.001] switch
80
Humidification control disable
Disable
humidification
control from bus =
yes
1 bit
C-W--
[1.002] boolean
81