Application manual
Air quality multisensor and regulator EK-ES2-TP
Release 1.0 - Updated: 14/02/2020
Application Manual
© EKINEX S.p.A. - All rights reserved
Page 66
7.10
TVOC control
The TVOC
control
folder allows to configure the parameters for the air quality functions management.
It includes the following secondary folders:
Thresholds
Condition: Internal sensors
TVOC sensor
TVOC control = enabled.
7.10.1
Thresholds
The secondary folder
Thresholds
includes the following parameters:
Threshold 1, along with the related value [ppb] and hysteresis;
Threshold 2, along with the related value [ppb] and hysteresis;
Threshold 3, along with the related value [ppb] and hysteresis;
TVOC ventilation;
Threshold 1;
Threshold 2;
Threshold 3.
7.10.1.1
Parameter and communication object tables
Parameter name
Conditions
Values
TVOC Threshold 1
– value [ppb]
220
[range
0 … 10000 ppb]
TVOC Threshold 1
– hysteresis
60
[other values in the 2
0 … 200 ppb
range]
TVOC Threshold 2
– value [ppb]
660
[range
0 … 10000 ppb]
TVOC Threshold 2
– hysteresis
60
[other values in the 2
0 … 200 ppb
range]
TVOC Threshold 3
– value [ppm]
2200
[range
0 … 10000 ppb]
TVOC Threshold 3
– hysteresis
60
[other values in the 2
0 … 200 ppb
range]
Ventilation
enabled /
disabled
TVOC Threshold x - Type
not active
/
below only /
above only /
below and above
x = 1, 2, 3