Application manual
Air quality multisensor and regulator EK-ES2-TP
Release 1.0 - Updated: 14/02/2020
Application Manual
© EKINEX S.p.A. - All rights reserved
Page 60
Object name
Conditions
Dim.
Flags
DPT
Comm. Obj.
No.
Relative humidity
control
dehumidification
dehumidification
function = cooling
only
Dehumidification integration
control
Temperature
control
Settings
Thermostat
function = both
heating and
cooling,
Temperature
control
cooling
cooling type =
floor radiant panels
or ceiling radiant
panels,
Relative humidity
control
dehumidification
dehumidification
function = cooling
only
Integration = yes
1 bit
CR-T-
[1.001] switch
78
This object switches ON if (simultaneously) the relative humidity is greater than the relative
humidity setpoint and the room temperature is greater than the setpoint of the parameter
Temperature difference for integration.
Dehumidification control disable
Disable
dehumidification
control from bus =
yes
1 bit
C-W--
[1.002] boolean
79