Application manual
Air quality multisensor and regulator EK-ES2-TP
Release 1.0 - Updated: 14/02/2020
Application Manual
© EKINEX S.p.A. - All rights reserved
Page 31
Object name
Conditions
Dim.
Flags
DPT
Comm. Obj.
No.
Room temperature (from bus)
enabled
2 bytes
C-WTU
[9.001]
temperature
(°C)
20
Humidity (2 bytes, from bus)
Relative humidity sensor =
enabled,
Humidity CO dimension = 2
bytes
2 bytes
C-WTU
[9.007]
humidity (%)
21
Humidity (1 byte, from bus)
Relative humidity sensor =
enabled,
Humidity CO dimension = 1
bytes
1 byte
C-WTU
[5.001]
percentage
(0..100%)
22
Indoor CO
2
value (from bus)
enabled
2 bytes
C-WTU
[9.001]
parts/million
(ppm)
139
Antistratification temperature (from
bus)
enabled
2 bytes
C-WTU
[9.001]
temperature
(°C)
23
Outdoor temperature (from bus)
enabled
2 bytes
C-WTU
[9.001]
temperature °C
24
Coil temperature (from bus)
enabled
2 bytes
C-WTU
[9.001]
temperature
(°C)
25
Floor temperature (from bus)
enabled
2 bytes
C-WTU
[9.001]
temperature
(°C)
26
Flow temperature (from bus)
enabled
2 bytes
C-WTU
[9.001]
temperature
(°C)
27
Anticondensation (from bus)
enabled
1 bit
C-WTU
[1.001] switch
33
Windows contact sensor 1 (from
bus)
enabled
1 bit
C-WTU
[1.019]
window/door
28
Windows contact sensor 2 (from
bus)
enabled
1 bit
C-WTU
[1.019]
window/door
29
Presence sensor 1 (from bus)
enabled
1 bit
C-WTU
[1.018]
occupancy
30
Presence sensor 2 (from bus)
enabled
1 bit
C-WTU
[1.018]
occupancy
31
Contact of card holder (from bus)
enabled
1 bit
C-WTU
[1.018]
occupancy
32