7.11
Ventilation
The secondary folder
Ventilation control – Settings
is the same for both CO
2
equivalente and TVOC
concentration.
It
includes the following parameters:
Communication object dimension;
Min. change of value to send [%];
Cyclic sending interval;
Value < threshold 1;
Threshold 1 < value < threshold 2;
Threshold 2 < value < threshold 3;
Threshold 3 < value;
CO
2
- Hysteresis (for continuous speed);
Min. CO
2
[ppm] value (for continuous speed);
Max. CO
2
[ppm] value (for continuous speed);
CO
2
Min. ventilation speed [%] output (for continuous speed);
CO
2
Max. ventilation speed [%] output (for continuous speed);
CO
2
ventilation lock;
Disable ventilation from bus;
Time scheduled ventilation.
The following condition has to be true:
o
Internal sensors
CO
2
sensor = enabled;
o
CO
2
control
Thresholds
CO
2
ventilation = enabled.
Or:
o
Internal sensors
TVOC sensor = enabled;
o
TVOC control
TVOC Thresholds
TVOC ventilation = enabled.
Or both the above conditions.
7.11.1.1
Parameter and communication object tables
Parameter name
Conditions
Values
CO
2
ventilation
disabled
/ enabled
TVOC ventilation
disabled
/ enabled
Ventilation
– Communication object dimension
CO
2
and/or TVOC ventilation =
enabled
4 single bit values /
1 byte unsigned value /
1 byte percentage
/
1 byte percentage (continuous speed)
Cyclic sending interval
CO
2
and/or TVOC ventilation =
enabled
no sending
[other values in the 30 s … 120 min
range]