Application manual
Air quality multisensor and regulator EK-ES2-TP
Release 1.0 - Updated: 14/02/2020
Application Manual
© EKINEX S.p.A. - All rights reserved
Page 83
Nr.
Communication object name
Size
Flags
Datapoint type
73
Thermostat - Dew-point temperature
2 bytes
CR-T-
[9.001] DPT_Value_Temp
74
Thermostat - Relative humidity setpoint for dehumidification
2 bytes
CRWTU [9.007] DPT_Value_Humidity
75
Thermostat - Relative humidity setpoint for humidification
2 bytes
CRWTU [9.007] DPT_Value_Humidity
76
Thermostat - Dehumidification command
1 bit
CR-T-
[1.001] DPT_Switch
77
Thermostat - Dehumidification water battery command
1 bit
CR-T-
[1.001] DPT_Switch
78
Thermostat - Dehumidification integration control
1 bit
CR-T-
[1.001] DPT_Switch
79
Thermostat - Dehumidification control disable
1 bit
C-W--
[1.002] DPT_Bool
80
Thermostat - Humidification command
1 bit
CR-T-
[1.001] DPT_Switch
81
Thermostat - Humidification control disable
1 bit
C-W--
[1.002] DPT_Bool
82
Thermostat - Anticondensation alarm
1 bit
CR-T-
[1.005] DPT_Alarm
83
Thermostat - Thermal generator lock
1 bit
C-W--
[1.005] DPT_Alarm
84
Thermostat - HVAC scene number
(not implemented)
1 byte
C-W--
[17.001] DPT_SceneNumber,
[18.001] DPT_SceneControl
85
Thermostat - Alarm text
14 bytes
CR-T-
[16.000] DPT_String_ASCII
86
CO
2
threshold 1 - Percentage
1 byte
CR-T-
[5.001] DPT_Scaling
86
CO
2
threshold 1 - Counter
1 byte
CR-T-
[5.010] DPT_Value_1_Ucount
86
CO
2
threshold 1 - Switch
1 bit
CR-T-
[1.001] DPT_Switch
87
CO
2
threshold 1 - Lock
1 bit
C-W--
[1.003] DPT_Enable
88
CO
2
threshold 2 - Percentage
1 byte
CR-T-
[5.001] DPT_Scaling
88
CO
2
threshold 2 - Counter
1 byte
CR-T-
[5.010] DPT_Value_1_Ucount
88
CO
2
threshold 2 - Switch
1 bit
CR-T-
[1.001] DPT_Switch
89
CO
2
threshold 2 - Lock
1 bit
C-W--
[1.003] DPT_Enable
90
CO
2
threshold 3 - Percentage
1 byte
CR-T-
[5.001] DPT_Scaling
90
CO
2
threshold 3 - Counter
1 byte
CR-T-
[5.010] DPT_Value_1_Ucount
90
CO
2
threshold 3 - Switch
1 bit
CR-T-
[1.001] DPT_Switch
91
CO
2
threshold 3 - Lock
1 bit
C-W--
[1.003] DPT_Enable
92
CO
2
ventilation bit 1 - switch
1 byte
CR-T-
[5.010] DPT_Value_1_Ucount
92
CO
2
ventilation - Counter
1 byte
CR-T-
[5.001] DPT_Scaling
92
CO
2
ventilation - Percentage
1 bit
CR-T-
[1.001] DPT_Switch
93
CO
2
ventilation bit 2 - switch
1 bit
CR-T-
[1.001] DPT_Switch
94
CO
2
ventilation bit 3 - switch
1 bit
CR-T-
[1.001] DPT_Switch
95
CO
2
ventilation bit 4 - switch
1 bit
CR-T-
[1.001] DPT_Switch
96
CO
2
ventilation - Lock
1 bit
C-W--
[1.003] DPT_Enable
97
CO
2
ventilation - Disable
1 bit
C-W--
[1.003] DPT_Enable
98, 103,
108, 113,
118, 123,
128, 133
Logic function x
1
– Input 1
1 bit
C-WTU
[1.001] DPT_Switch
99, 104,
109, 114,
119, 124,
129, 134
Logic function x
– Input 1
1 bit
C-WTU
[1.001] DPT_Switch
100, 105,
110, 115,
120, 125,
130, 135
Logic function x
– Input 1
1 bit
C-WTU
[1.001] DPT_Switch
1
“x” can span from 1 to 8.