Parameter name
Conditions
Values
Control type
Thermostat function = both heating
and cooling
Command Communication Object
= unique
continuous /
PWM (pulse width modulation) /
2-points hysteresis
/
6-way valve
It allows to configure the temperature control type.
Heating
– cooling switch over
Thermostat function = both heating
and cooling
Control type = 6-way valve
from bus
/
automatic
Heating-cooling cyclic sending interval
Thermostat function = both heating
and cooling
no sending
[other values in the range
30 s … 120
min]
HVAC mode after download
Thermostat function = both heating
and cooling
no change
heating
cooling
Setpoint cyclic sending interval
no sending
[other values in the range
30 s … 120
min]
The setpoint value that can be sent cyclically is the actual one, depending on the
operating mode set manually by the user or automatically by another KNX
supervising device with the possibility of time scheduling. The actual setpoint value
takes also into account the actual state of the contacts window and presence
detection (if the corresponding functions are enabled).
End of manual operation
till first telegram from bus
[other values in the range
30 min … 48 h]
Disable temperature controller from bus
no
/ yes
It defines the possibility to disable the temperature controller function via bus.
Signal from bus
Disable temperature controller
from bus = yes
not inverted
/ inverted
It defines the logic for the signal that enables or disabled the temperature controller
function via bus.
Transmission delay after mode change
00:00:04.000
(hh:mm:ss)
(range 00:00:00.000 – 00:10:55.350)
Valve protection function
disabled
/ enabled
It enables the function that activates the drive for the valve control during periods
of inactivity of the system.
Frequency
Valve protection function = enabled
once a day
once a week
once a month
Time interval
Valve protection function = enabled
10 s
[other values in the range
5 s … 20 min]
Object name
Conditions
Dim.
Flags
DPT
Comm.
Obj.
No.
Actual setpoint
2 bytes
CR-T-
[9.001] temperature (°C)
43