Application manual
Air quality multisensor and regulator EK-ES2-TP
Release 1.0 - Updated: 14/02/2020
Application Manual
© EKINEX S.p.A. - All rights reserved
Page 20
7.3
Internal sensors
The
Internal sensors
folder includes the following parameters:
Temperature sensor enabling
Relative Humidity sensor enabling
CO
2
equivalent sensor enabling
TVOC sensor enabling
7.3.1
Temperature sensor
The
Temperature sensor
folder contains the following parameter:
Filter type for the internata data computing
Temperature offset, applied to the measured value
Minimum change of value to send [K]
Cyclic sending interval
Threshold 1
Threshold 2
7.3.1.1
Parameter and communication objects tables
Parameter name
Conditions
Values
Temperature sensor
enabled
disabled
The temperature sensor is enabled as default.
Filter type
Temperature sensor = enabled
low
medium
high
Low = average value every 4 measurements
Medium = average value every 16 measurements
High = average value every 64 measurements
Temperature offset
Temperature sensor = enabled
0°C
[range -5°C … +5°C]
Minimum change of value to send [K]
Temperature sensor = enabled
0,5
[range 0 …5]
If the parameter is set to 0 (zero), no value is sent after a change.
Cyclic sending interval
Temperature sensor = enabled
no sending
[other values in the range 30 s … 120 min]
Threshold 1
Temperature sensor = enabled
not active
below
above
Value [°C]
Temperature sensor = enabled,
Threshold 1 = below or above
7
[range 0 … 50]
Threshold value update from bus
Temperature sensor = enabled,
Threshold 1 = below or above
no
/ yes
Threshold lock enable
Temperature sensor = enabled,
Threshold 1 = below or above
no
/ yes