Outdoor temperature
disabled
/ enabled
It enables an outdoor temperature bus sensor to display the measured value
on the display. This is alternative to an outdoor temperature sensor connected
to a device input: the parameter appears only if the external temperature
sensor is disabled in the Inputs folder.
Light sensor
disabled
/ enabled
Cyclic reading interval
Light sensor = enabled
no reading
[other values in the range 30 s … 120 min]
Coil temperature
disabled
/ enabled
It enables a bus sensor for measuring the coil temperature of the conveying
fluid for heat exchange. The acquisition of the value allows realizing the hot-
start function of a fan.
Cyclic reading interval
Coil temperature = enabled
no reading
[other values in the range 30 s … 120 min]
Floor surface temperature
disabled
/ enabled
It enables a bus sensor for measuring the surface temperature of a floor
heating system. The acquisition of the value allows to realize the function of
surface temperature limitation.
Cyclic reading interval
no reading
Floor surface temperature = enabled
[other values in the range 30 s … 120
min]
Flow temperature
disabled
/ enabled
It enables a bus sensor for measuring the flow temperature of the conveying
fluid. The acquisition of the value allows calculating the dew-point temperature
to realize the active anticondensation protection function in surface cooling
plants (floor or ceiling).
Cyclic reading interval
no reading
Flow temperature = enabled [other
values in the range 30 s … 120
min]
Analog sensors timeout
00:05:00hh:mm:ss
[range
00:00:00 … 18:12:15]
The field has format hh:mm:ss (hours : minutes : seconds): the default value
00:05:00 corresponds to a timeout of 5 minutes. The value 00:00:00 means
that the timeout of the analogic sensors is disabled.
Anticondensation
disabled
/ enabled
It enables a bus sensor for detecting the condensation.
Signal
Anticondensation = enabled
not inverted
/ inverted
Cyclic reading interval
Anticondensation = enabled
no reading
[other values in the range 30 s … 120 min]
Window contact 1
disabled
/ enabled
It enables a bus sensor for detecting the state of opening / closing of a window
or a door.