Applicatio Manual
Universal Interface 4 DIN/NTC EK- CG2-TP
Revisione 1.0.0 - Aggiornato: 04/09/2017
© SBS S.p.A.
– Tutti i diritti riservati
MAEKCG2TP_EN
Pag. 51
Setpoint cyclic sending interval
no sending
[other values in the range 30 s … 120 min]
The setpoint value that can be sent cyclically is the actual one, depending on the
operating mode set manually by the user or automatically by another KNX
supervising device with the possibility of time scheduling. The actual setpoint value
takes also into account the actual state of the contacts window and presence
detection (if the corresponding functions are enabled).
Max manual temperature change
not allowed, ± 1°C, ± 2°C,
± 3°C
, ± 4°C, ±
5°C, ± 6°C, ± 7°C, ± 8°C, ± 9°C, ± 10°C
It defines the maximum range allowed for the manual change of the temperature
value.
End of manual operation
General Device operation as =
till first telegram from bus
stand-alone
[other values in the
range 30 min … 48 h]
Exit manual mode on setpoint from bus
no
/ si
It defines the exit from manual/forced mode in case of setpoint modification on bus
(communication objects index from 29 to 36)
Max setpoint temperature change
not allowed, ± 1°C, ± 2°C, ± 3°C, ± 4°C,
± 5°C, ± 6°C, ± 7°C, ± 8°C,
± 9°C
, ± 10°C
It defines the maximum time allowed for changing the values of temperature
setpoint in the several operating modes.
Duration of comfort extension
General Device operation as =
not allowed
, slave [other values in the
range 15 min … 4 h]
When device operation as = slave, if the operating mode forced by the time
scheduling is not comfort or building protection, this parameter defines the
maximum duration of temporary comfort before returning to the programmed
operating mode.
Scenes
disabled
/ enabled
Transmission delay after mode change
Valve protection function
disabled
/ enabled
It enables the function that activates the drive for the valve control during periods of
inactivity of the system.
Frequency
Valve protection function = enabled
once a day
once a week
once
a month
Time interval
Valve protection function = enabled
10 s
[other values in the range 5 s … 20 min]
Object name
Conditions
Dim.
Flags
DPT
Comm.
Obj.
No.
Actual setpoint
2 Byte
CR-T--
[9.001] temperature (°C)
27
Manual setpoint
2 Byte
C-W---
[9.001] temperature (°C)
28