Parameter name
Conditions
Values
Hysteresis
Control type = 2 point hysteresis
0,3 K
[other values in the range 0,2 K … 3 K]
Hysteresis position
Heating type = floor radiant panels, ceiling
radiant panels,
Control type = 2 point hysteresis
below
/ above
The above hysteresis is suitable in case of special applications requiring mixing group
control.
Cyclic sending interval
Control type = 2 point hysteresis or
continuous
no sending
[other values in the range 30 s … 120
min]
Min. change of value to send [%]
Control type = continuous
10
[range 0 … 100]
PWM cycle time
Control type = PWM (pulsa width
modulation)
15 min
[range 5 … 240 min]
Proportional band [0,1 K]
Control type = continuous or PWM
*
[range 0 … 255]
The value is in tenths of Kelvin (K) degree.
*) The field contains a preset value that depend on the selected cooling type (the value
can be modified):
•
fan-coils: 40 (4 K)
•
floor radiant panels: 50 (5 K)
•
ceiling radiant panels: 50 (5 K)
The value of the parameter Proportional band represents the max difference between
the setpoint temperature and the measured temperature that causes the max control
output.
Integral time [min]
Control type = continuous or PWM
*
[range 0 … 255 min]
*) The field contains a preset value that depend on the selected cooling type (the value
can be modified):
fan-coils: 90 min
•
floor radiant panels: 240 min
•
ceiling radiant panels: 180 min
Min control value [%]
Control type = continuous or PWM
15
[range 0 … 30]
Max control value [%]
Control type = continuous or PWM
85
[range 70 … 100]
Anticondensation with probe
Cooling type = floor radiant panels or
ceiling radiant panels,
External sensors (from bus)
Anticondensation = enabled
disabled
/ enabled