9.10 Energy saving
In order to realize energy-saving functions, window contacts (to detect the opening of windows or doors), presence and
movement sensors and card holders can be used.
The
Energy saving
folder includes the following secondary folders:
•
Window contacts
•
Presence sensors
•
Card holder
9.10 .1 Window contacts
The
Window contacts
secondary folder appears if at least a sensor dedicated to this function is enabled i.e. if the
following condition is verified: External sensors (from bus) Windows contact sensor 1 or 2 (from bus) = enabled
The
Window contacts
folder includes the following parameters:
•
Window contacts function
•
Wait time to building protection mode
9.10.1.1 Parameter and communication object tables
Parameter name
Conditions
Values
Window contacts function
disabled
/ enabled
This parameter enables the window contact function.
Wait time to building protection mode
00:01:00 hh:mm:ss
Window contacts function = enabled
[range 00:00:00 … 18:12:15]
Time interval before the automatic switching of the device to the Building protection
operating mode
Nome oggetto
Conditions
Dim.
Flags
DPT
Comm.
Obj. No.
Windows contact sensor 1
(from bus)
Window contacts function =
enabled,
Window contact 1 = enabled
1 Bit
C-W--
[1.019]
window/door
13
Windows contact sensor 2
(from bus)
Window contacts function =
enabled,
Window contact 2 = enabled
1 Bit
C-W--
[1.019]
window/door
14
9.10.2 Presence sensors
The
Presence sensors
folder includes the following parameters:
•
Presence sensor function
•
Presence sensors use
•
Thermostat modes
•
Absence time to switch HVAC mode