Installation and Startup of UA 410 L
40
Firmware V1.50 - Doku 2.0 06. April 2016
5.10 Firmware Update
The case controller is supplied with the current firmware, ready for operation. Future software versions can be
loaded into the case controller as required by means of a firmware update, and thus updated.
A software update is only to be carried out by trained staff or factory-side by the manufacturer.
Damage to equipment and goods!
Before the firmware update the affected component, i.e. equip
ment must be brought into a safe state as the deactivation of the controller during the firmware up
date can have undesired effects on the component, i.e. equipment.
Danger data loss!
The loading of software via firmware update must not be interrupted. The power
cable and USB A-B cable must not be disconnected during the firmware update. It must be ensured
that power is supplied throughout the entire procedure. An interruption of the firmware update can
result in an inoperative controller. In some cases a change of firmware version can lead to the loss
of all the setpoints in the case controller. As a precaution, the settings
should
be backed up by sav
ing them to the LDSWin PC software,
prior
to the update.
After the firmware update the backup settings can be reloaded into the case controller from LDSWin.
5.10.1 Firmware Update requirements
The following components are required for a firmware update:
- Notebook or PC
- USB A-B cable
(Accessories)
- The installation program ”
Firmware_Uploader_Setup_vxx.exe
”
(available from manufacturer)
- Current firmware in the binary file ”
UA400_vx.xx.bin
”
(available from manufacturer)
Administrator rights required during initial installation!
With the operating systems Windows 2000, XP, Vista and Windows 7, the user
must
have
adminis
trator rights
during installation when the installation program ”
Firmware_Uploader_Setup_vxx.exe
”
is being executed. Administrator rights will also be required when the controller is initially connected
to the PC and the driver is installed by the operating system.
Following installation and the initial connection of the controller to the PC administrator rights are no
longer required.
In the event of questions concerning administrator rights under Windows, the responsible IT admin
istrator should be consulted.
Summary of Contents for UA 410 L Case Controller
Page 30: ...Function of UA 410 L 24 Firmware V1 50 Doku 2 0 06 April 2016 Notice...
Page 52: ...Installation and Startup of UA 410 L 46 Firmware V1 50 Doku 2 0 06 April 2016 Notice...
Page 72: ...Operation of UA 410 L 66 Firmware V1 50 Doku 2 0 06 April 2016 Notice...
Page 80: ...Menu Structure of UA 410 L 74 Firmware V1 50 Doku 2 0 06 April 2016 Notice...
Page 82: ...Decommissioning and disposal 76 Firmware V1 50 Doku 2 0 06 April 2016 Notice...
Page 92: ...Order numbers and accessories of UA 410 L 86 Firmware V1 50 Doku 2 0 06 April 2016 Notice...