Installation and Startup of UA 410 L
25
Firmware V1.50 - Doku 2.0 06. April 2016
5
Installation and Startup of UA 410 L
Important safety instructions!
Before the installation and commissioning of the controller, chapter 1
should be carefully read in its entirety and all safety instructions and hazard warnings observed.
The controller should only be used with compatible versions of the PC software LDSWin, otherwise
the range of functions could be restricted.
Tip
: The latest version of LDSWin should be used at all times.
5.1
Installation
The Temperature Data Logging Controller is produced in the type UA 410 L AC.
5.1.1
DIN rail mounting of the Temperature Data Logging Controller
The power loss of the device is approx. 11 VA and must be taken into account for the installation.
Similar to illustration
The Temperature Data Logging Controller is attached to the DIN rail (35 mm) using two retaining springs. The
DIN rail must have a minimum height of 5 mm.
The Temperature Data Logging Controller may only be mounted on a Cap (DIN) rail and
operated as an integrated regulation and control device (EN60730).
All leads running to and from the case controller - especially those of the CAN bus - must be
shielded (cable type: LiYCY)! No shielding is required on sensor leads when installed exclusively
inside the refrigerated display case and when external interference (for example from parallel power
wires) is not to be expected (see operating instruction “Introduction, General Safety and Connection
Instructions”). As a general rule, care should be taken to ensure that signal leads and leads carrying
a supply voltage are routed through separate cable channels.
Electrical enclosure and dimensions are listed in Section Specifications.
Summary of Contents for UA 410 L Case Controller
Page 30: ...Function of UA 410 L 24 Firmware V1 50 Doku 2 0 06 April 2016 Notice...
Page 52: ...Installation and Startup of UA 410 L 46 Firmware V1 50 Doku 2 0 06 April 2016 Notice...
Page 72: ...Operation of UA 410 L 66 Firmware V1 50 Doku 2 0 06 April 2016 Notice...
Page 80: ...Menu Structure of UA 410 L 74 Firmware V1 50 Doku 2 0 06 April 2016 Notice...
Page 82: ...Decommissioning and disposal 76 Firmware V1 50 Doku 2 0 06 April 2016 Notice...
Page 92: ...Order numbers and accessories of UA 410 L 86 Firmware V1 50 Doku 2 0 06 April 2016 Notice...