Installation and Startup of UA 410 L
34
Firmware V1.50 - Doku 2.0 06. April 2016
5.6
Basic configuration of the controller
The lock-down must previously be deactivated on the higher level controller (system centre / store computer or
operator terminal) so that configuration settings can be made on the controller.
1.
Deactivating the input lock-down
A. BT 300 operator interface
See chapter 7.2.1 for details.
B. System centre
Via Login symbol; see chapter 7.3.3.1 for details.
C. Store computer / operator terminal
Menu 9-3; see chapter 7.3.3.2 for details.
2.
Opening main menu of the controller
A. The main menu of the controller is shown directly in the operator interface.
B. In the system centre, select the required controller in
Menu 4-2
and then tap the
Remote Control
button to
display the main menu of the controller. See chapter 7.3.2.1 for details.
.
C. In the store computer and operating terminal, a selection list of all CAN bus components is displayed in Menu
5 Remote Control. Select the controller with the corresponding CAN bus address (Kn,nnn = 1..99) in the selec
tion list to be parametrised using the cursor or direct input and recall by tapping the
ENTER
button (
↵
) so that
the main menu of the controller is displayed. See chapter 7.3.2.2 for details.
2a. Special case UA 410 L
In contrast to the other controllers in the UA 400 series, the required sensor must be selected previously
on the UA 410 L to reach the main menu of any temperature sensor (Rx.1 ... Rx0):
Main Menu
REFR. PT.
POS: XXX
1 Temp. Rx.1
Selection field 1st temperature sensor Rx.1 - Text freely selectable, see Menu 6-1
2 Temp. Rx.2
Selection field 2nd temperature sensor Rx.2 - Rx.2 - Text freely selectable, see
Menu 6-1
...
...
0 Temp. Rx.0
Selection field 10th temperature sensor Rx.0 - Text freely selectable, see Menu 6-1
Summary of Contents for UA 410 L Case Controller
Page 30: ...Function of UA 410 L 24 Firmware V1 50 Doku 2 0 06 April 2016 Notice...
Page 52: ...Installation and Startup of UA 410 L 46 Firmware V1 50 Doku 2 0 06 April 2016 Notice...
Page 72: ...Operation of UA 410 L 66 Firmware V1 50 Doku 2 0 06 April 2016 Notice...
Page 80: ...Menu Structure of UA 410 L 74 Firmware V1 50 Doku 2 0 06 April 2016 Notice...
Page 82: ...Decommissioning and disposal 76 Firmware V1 50 Doku 2 0 06 April 2016 Notice...
Page 92: ...Order numbers and accessories of UA 410 L 86 Firmware V1 50 Doku 2 0 06 April 2016 Notice...